7-4 The Keypad Installation Manual
Connecting the Keypad
to the Controller
You will need 22-gauge 4-conductor plenum-
rated cable for installation. If you are using
composite cable, see Chapter 2 for color code.
If you are going to connect the Tag Detect signal
to the auxiliary LED of the Keypad, you will
need at least a 5-conductor cable.
To connect the Keypad to the Controller, refer to
Figures 7.3 – 7.4 and use the following
instructions:
1. Separate the Keypad from the white
back box.
2. Remove the Controller cover.
3. Feed the cable from the Controller to the
Keypad through the raceway, conduit, or
wall and then through the access hole
you made in the white back box.
4. With the WHITE wire, pin 1 of the
Keypad to P8-pin1 (Kypd Alarm) of the
Controller.
5. With the BLACK wire, connect pin 6 of
the Keypad to P8-pin2 (Ground) of the
Controller.
6. With the RED wire, connect pin 10 of
the Keypad to P8-pin3 (+12v) of the
Controller.
7. With the GREEN wire, connect pin 11
of the Keypad to P8-pin4 (Kypd Reset)
of the Controller.
8. If you are using the Tag Detect option
(
Figure 7.4), with the BROWN wire,
connect pin 4 of the Keypad to P8-pin5
(Tag Detect) of the Controller.
9. Place a jumper connecting the Keypad
pins 2, 4 and 6.
NOTE: If using Tag Detect option, only
jumper Keypad pins 2 and 6.
10. Place a jumper connecting the Keypad
pins 3, 7 and 10.
11. Replace the Controller cover.
12. Replace the Keypad to the white back