User's Manual

Installation Manual Power Supply 18-1
Power Supply
Power Supply Specifications
Positioning the Power Supply
Mounting the Power Supply
Connecting the Power Supply
Some installations of the Accutech System
peripherals require more power than the
Controller can provide. In these cases, a Power
Supply (
Figure 18-1) is added to the system to
meet the additional power requirements.
Power Supply Specifications
Power
Temperature
Weight
Power
120V AC, 2 amp
Temperature
A Power Supply operates best in an ambient
temperature between 35 and 90 degrees
Fahrenheit. Operation outside of this range may
cause unexpected or undesirable results,
including premature failure.
Weight
A Power Supply weighs approximately 12
pounds.
Positioning the Power Supply
The Power Supply is located above the drop
ceiling or remotely in a utility closet near a
120V AC dedicated power outlet.
Mounting the Power Supply
Use appropriate hardware for the weight and
mounting surface.
Connecting a Power Supply
For all connections to the Power Supply, use 18-
gauge, 2-conductor wire. To connect a Power
Supply, refer to Figure 18.1 and the respective
component:
To a GDP
To a FPI
To a BR 4200 Receiver
To a Multiplexer
To a GDP
Using RED and BLACK wire, connect the +12V
and Ground between the Power Supply terminal
strip and GDP.
To a FPI
Using RED and BLACK wire, connect the +12V
and Ground between the Power Supply terminal
strip and FPI.
To a BR 4200 Receiver
NOTE: Connections between the BR 4200
Receiver(s) and Multiplexer should be
completed first (
see pages 17-3 - 17-5).
Using RED and BLACK wire, connect the
+12V and Ground between the Power Supply
terminal strip and FPI.
To a Multiplexer
NOTE: Connections between the Multiplexer
and BR 4200 Receiver(s) should be completed
first (
see pages 17-3 and 17-5).
Using RED and BLACK wire, connect the +12V
and Ground between the Power Supply terminal
strip and Multiplexer.