User's Manual

21-2 Band Removal Lockdown Installation Manual
6. For each Controller (Lock) you must
pick a set of contacts to work with on
the Relay Board. The example in Figure
21.1 shows Relay K1 being used:
a. Connect P8-3 (+12V) on the
Controller to J1 at (K1-Com) on
the 8-zone Relay Board.
b. Connect P6-1 (Per. Lock) on the
Controller to J1 at (K1-NO) on
the 8-zone Relay Board.
7. Do the same for contact K2 through K8.
8. If more than 8 zones are being locked,
then additional Relay boards will need
to be connected.
a. Connect +12V and GND of the
each Relay Board in parallel to
+12V and GND of the first
Relay Board.
b. Tie pins B1 through B8 of each
Relay Board to one common
point together on that Relay
Board and connect the common
point of each Relay Board to the
external 12V DC relay at COM
position.
9. Repeat step 7 for each Controller (Lock)
choosing a different set of contacts (K1-
K8) of the Relay Board for each zone to
be locked down when a Band Removal
alarm occurs.