Instruction Manual

USER INSTRUCTIONS
86BIQ00006 2012-10
The transmitter is congured from a standard IBM compatible PC by
using the IPRO-Software version 4.14 or later. The latest version
of IPRO can be downloaded from http://www.inor.com. When the
transmitter is set from a PC no calibration is needed.
When calibrate/congure ”online” with the input con-
nected to hazardous area the ATEX certied version of IPRO-X
cable must be used.
The transmitter is polarity protected and will not be damaged by
connecting the power supply with the wrong polarity, but the output
will be 0 mA.
The maximum load in the output loop depends on the supply voltage,
see ”DATA shortform”
”Isolation input/output/PC” mentioned in the data sheet,
indicates signal isolation only. It shall not be interpreted as
an IS galvanic isolation like an isolating barrier. Therefore
ordinary care in selecting barrier and grounding should be
considered for the IPAQ-LX. Maximum common-mode voltage
on the input is restricted to 50 VAC / 75 VDC.
Sensor wire check: the transmitter uses a pulsating technique to
monitor sensor break or sensor shortened to avoid measuring errors.
This pulsating signal may interfere with some electronic calibrators.
By selecting Sensor Break = None in the IPRO software and
download the conguration into the transmitter the pulsating signal
is turned off.
GENE R AL INFORM ATION
INTR O DUCTION
IPAQ-L is a universal and intelligent 2-wire rail-mounted transmitter
for temperature and other measurement applications.
IPAQ-LX is the Intrinsic Safe version for use in Ex-applications.
IPAQ-L(mA) is a version for current input only, up to 50 mA.
DIME N SIONS
Intelligent 2-wire
DIN Rail Temperature & mA
Transmitters
CONF I GURATION
The IPAQ-L/LX transmitter must be powered, when you congure the
transmitter, (see ”Connectionsg.1). If IPRO (the IPAQ software) isn’t
installed in your PC, install the software.
For keeping the safety of the internal circuits in the
IPAQ-LX, always use Ex-power supply or a zener barrier with
limitations according to Ex-data and IPRO-X conguration
cable when making a conguration.
When choosing differential temperature measuments with Pt100 be
sure to select ”sensor break” = none.
Conguration from PC is ”on-line”, that is, the transmitter can be con-
gured while in operation if the area is known to be non-hazardous.
The output is frozen while transmission from PC to IPAQ take place.
When transfer is done the transmitter uses the new parameters.
1
2
4
3
5
6
7
!
MEA SUR E O F S UCC ESS
The user instruction must be read prior to adjustment and/or installation.
All information subject to change without notice.
MEA SUR E O F S UCC ESS
This product should not be mixed with other kind of scrap, after usage.
It should be handled as an electronic/electric device.
www.inor.com, www.inor.se
ATEX
!
!
INOR Process AB, PO Box 9125, SE-200 39 Malmö, Sweden,
Phone: +46-40-31 25 60, Fax: +46-40-31 25 70, E-mail: support@inor.se
INOR Transmitter OY, Unikkotie 13, FI-01300 Vantaa, Finland,
Phone:+358-10-421 7900, Fax: +358-10-421 7901, E-mail: support.@inor.se
INOR Transmitter GmbH, Am Bocksborn 5,
D-63571 Gelnhausen, Germany,
Phone: +49-6051 14807, Fax: +49-6051 14806, E-mail: support.de@inor.se
KROHNE Temperature Division INOR, 7 Dearborn Road,
Peabody, MA 01960, USA,
Phone: +1-978-826 6900, Fax: +1-978-535 3882, E-mail: inor-info@krohne.com

Summary of content (2 pages)