Voltage Regulator-Down (VRD) 10.0
Processor Voltage Requirements
R
18 VRD Design Guide
To properly calibrate the socket loadline parameter, the VR designer must excite the processor
socket with a current step that generates a voltage droop which must be checked against the
loadline window requirements. The table below identifies the steady state and transient current
values to use for this calibration. For additional information, please consult the Loadline
Calculator for the appropriate Intel processor.
Table 10. Intel
®
Processor Current Step Values for Transient Loadline Testing
VR Configuration Starting Current Ending Current Dynamic Current Step
478_VR_CONFIG_A 21 A 91 A 70 A
478_VR_CONFIG_B 23 A 78 A 55 A
478_VR_CONFIG_C 20 A 70 A 50 A
478_VR_CONFIG_D 21 A 91 A 70 A
VRD designs must be loadline compliant across the full tolerance band window to avoid data
corruption, system lock-up, and reduced performance. When validating a system’s loadline, a
single measurement is statistically insignificant and cannot represent the response variation seen
across the entire high volume manufacturing population of VRD designs. A typical loadline may
fit in the specification window, however designs residing elsewhere in the tolerance band
distribution may violate the specifications. For example, Figure 5 Example A shows a loadline that
is contained in the specification window and, in this single instance, complies with Vccmin and
Vccmax specifications. The positioning of this loadline will shift up and down as the tolerance
drifts from typical to the design limits. Figure 5 Example B shows that Vccmax limits will be
violated as the component tolerances shift the loadline to the upper tolerance band limits. Figure 5
Example C shows that the Vccmin limits will be violated as the component tolerances shift the
loadline to the lower tolerance band limits.
To satisfy specifications across high volume manufacturing variation, a typical loadline must be
centered in the loadline window and have a slope equal to the value specified in Table 4. Figure 6
Example A shows a loadline that meets this condition. Under full 3-sigma tolerance band
variation, the loadline slope will intercept the Vccmax loadline (Figure 6 Example B) or Vccmin
loadline (Figure 6 Example C) limits.