Voltage Regulator-Down (VRD) 10.1 Design Guide

Processor Vcc Requirements
R
Design Guide 27
condition does not occur. In addition, reverse current into the AC-DC regulator must not impair
the operation of the VRD, the AC-DC supply, or any other part of the system.
Under all functional conditions, including D-VID, the Vcc supply must satisfy load line and
overshoot constraints to avoid data corruption, system lock-up events, or system blue-screen
failures.
Figure 2-6. Processor D-VID Load Line Transition States
Vcc (Voltage)
Icc (Amperes)
Original VID
Load Line Window
Low Voltage VID
Load Line Window
1
2
3
4
5
D-VID Vmax
Load Line
Vmin Load Line
D- VID Vmin Load Line
Vmax Load Line
2.6.2 D-VID Validation
Intel processors are capable of generating numerous D-VID states and the VRD must be designed
to properly transition to and function at each possible VID voltage. However, exhaustive
validation of each state is unnecessary and impractical. Validation can be simplified by verifying
the VRD conforms to socket load line requirements, tolerance band specifications, and D-VID
timing requirements. Then, by default, each processor D-VID state will be valid. The key
variables for Vcc under D-VID conditions are processor loading, starting VID, ending VID, and
Vcc slew rate. The Vcc slew rate is defined by VRD bulk decoupling, the output inductors, the
switching FET resistance and the processor load. This indicates that the Vcc slewing will have an
exponential behavior, where the response to code ā€˜n+1’ takes longer to settle than code ā€˜n’. As a
result, a test from maximum to minimum and from minimum to maximum will be sufficient to
guarantee slew rate requirements and VID code regulation.
To ensure support for any valid VID reference, testing should be performed from the maximum
table entry of 1.6 V to the minimum value of 0.8375 V. The VRD must ensure that this 0.7625 V
transition occurs within 50 microseconds of the final VID code, in 350 microseconds. Slew rate
timing is referenced from 0.4 V on the rising edge of the initial VID code to the time the final
voltage is settled within 5 mV of the final Vcc value. Intel testing has noted a 10% change to the