Instructions

19" Intelligent 8-Port PDU User Manual
8
. ON and OFF Time Delay
Click “PDU” in the configuration box on the left side of the interface. The screen displays the following:
This function lets you adjust delay times in the start-up and shut-off sequences for connected equipment. In
the default settings shown here, power is supplied to and shut off from all ports in one-second intervals
after five seconds have passed from a start-up or shut-down command. Change values by entering them into
the fields and click Apply. NOTE: When input power is disconnected from its source, the OFF Delay function
is ignored, and power shuts off immediately to all equipment. Shutting off the time-delay function only
applies to the devices connected to the PDU.
. Threshold Value Setting
Click “Threshold value” in the configuration box on the left side of the interface. The screen displays the following:
The meaning of each input is as follows; adjust values here and click Apply when finished:
Current Warning value (5.0 A) if total current exceeds 5 A, the PDU will beep twice;
Current Overload value (6.0 A) if total current exceeds 6 A, the PDU will shut off power to all
output ports;
Warning Voltage value (250) if input voltage exceeds 250 V, the PDU will beep twice;
Voltage Overload value (300) if input voltage exceeds 300 V, the PDU will shut off power to all
output ports;
Temperature is Under (5°C) or Above (50°C): if the built-in temperature sensor reads temperatures under or
over these thresholds, the PDU will beep twice;
Humidity Warning value (80%): if the built-in humidity sensor reads humidity at more than 80%, the PDU
will beep twice.