Product Data Sheet / Brochure
Interactive Front-Panel LCD
Reports detailed status information, including load and battery levels
Offers advanced configuration options, including output voltage and power strategies
5 Power Strategies
Auto Adaptive enables high efficiency and high-quality operation as necessary for ideal equipment protection
Max Efficiency favors economy operation with high 95% efficiency
Max Quality favors on-line, double-conversion mode, maintaining +/-2% output voltage regulation and zero transfer time
Frequency Regulation and Frequency Conversion enable +/-0.05 Hz output regulation for selected frequency(50/60 Hz)
Reliable, Expandable Battery Backup
Supports half load(1350W) for 13.5 min. and full load(2700W) for 5 min.
Add external battery packs for extra runtime
“Smart” battery packs, such as Tripp Lite’s BP72V18-2US, are automatically sensed and configured during replacement
Full 2700W capacity available with and without external battery packs
Electronic Bypass
Maintains utility output during UPS fault conditions
Adjustable bypass range and high-efficiency mode voltage settings
Highly Customizable
Customize communications and behavior to integrate with device makers' specific needs
Selectable auto-restart from 0 to 60 sec. after AC power is restored
Selectable minimum battery charge level before auto-restart
Schedule system reboot if USB signal from connected device is lost
Set overload thresholds and low battery levels for alert and shutdown
Remote on/off(toggle) support via DB9
SNMP/Web Capability
Optional Tripp Lite SNMPWEBCARD permits remote management of UPS, including reboots, configuration, updates and activity logs
Specifications
OUTPUT
Output Volt Amp Capacity (VA) 3000
Output kVA Capacity (kVA) 3
Output Watt Capacity (Watts) 2700
Output kW Capacity (kW) 2.7
2 / 6