Data Sheet

www.GE-Interlogix.com
GE Interlogix
Product Information
Standard Features
Single action
Dual action
Terminal connections
Die cast aluminum alloy
Semi-flush or surface mounting
Weatherproof models available
UL Listed
Manual Fire Alarm Stations
Single & Dual Action
103 Series
The 103 Series fire alarms are manually operated non-coded
devices for initiating fire alarm signals. The pull handle latches
until the station is reset by operating the station cover.
Operation of the pull handle closes a single-pole or double-pole
switch. Two wire barrier terminals are provided, each
accommodating two conductors, #14 AWG or smaller. Opening
the cover also closes the alarm initiating switch to allow testing.
Both 103-22 (Hex key reset) and 103-42 (cat 30 key reset) are dual
action stations that are provided with a cover which must be
lifted to expose the pull handle. A break-glass rod is included with
each station for optional use.
For outdoor or harsh environment applications, use the 103-60
(water/weatherproof single action station).
The 103 Series manual fire alarm stations are intended for use as
fire alarm initiating devices, with any fire alarm initiating circuit to
be operated by a contact closure rated not more than 10 amperes,
125 V AC.
The 103 Series manual fire alarm stations mount to standard
single-gang electrical boxes or to a plaster ring. The maximum
depth of the equipment is 1
1
/4”.
Model 103-25 surface mounting box is availble. The box is
5” high x 3
1
/4” wide x 2
3
/4” deep.
All stations should be installed in compliance with the
application NFPA standards, local building codes, and plans
and specifications.