Installation Manual Instruction Manual

Appendix A: System planning sheets
120 Concord 4 Installation Manual
Part number
Description
Quantity
mA
(max.)
Subtotal
60-804
2x20 VFD alphanumeric touchpad
120 mA
60-983
ATP 1000
110 mA
60-984
ATP 2600
165 mA
60-985
ATP 2100
300 mA
600-1013
GTS 50
300 mA
60-836
Voice only module (with current jumper
installed) / (with current jumper removed)
300 mA /
600mA
60-777-01
Phone interface/voice module
600 mA
600-1019
2-amp power supply
N/A
60-756
4 input/2 output SnapCard
185 mA
60-757
8Z hardwired zone expander SnapCard
230 mA
60-758
4 output SnapCard
130 mA
60-774
Hardwired input module
35 mA
60-770
Hardwired output module
180 mA
60-620-01
Energy saver module
20 mA
60-850
60-850-01
Cellular backup module (standard power)
Cellular backup module (high power)
10 mA
60-861
Wireless cellular gateway
1900 mA
60-677
Interrogator 200 audio verification module
1600 mA
60-783-02
Automation module
10 mA
60-528
Hardwired interior speaker
35 mA
13-060
15-watt speaker
500 mA
Total power consumption:
Total power consumption not to exceed:
mA
1,000 mA