Installation Manual Instruction Manual

Chapter 2: Installation
8 Concord 4 Installation Manual
Table 4 below describes the maximum wire length allowed between compatible
devices and the panel, and the minimum and maximum current draw of each
device.
Table 4: Wire length requirements
Device
Max. wire
length to
panel
Standby mA
draw
Alarm mA draw
SuperBus 2000 2x16 LCD alphanumeric
touchpad
22 ga.: 300 ft.
18 ga.: 750 ft.
15 mA
90 mA
SuperBus 2000 ATP 1000 alphanumeric
touchpad
22 ga.: 300 ft.
18 ga.: 750 ft.
12 mA
110 mA
SuperBus 2000 ATP 2100 alphanumeric
touchpad
22 ga.: 300 ft.
18 ga.: 750 ft.
30 mA
165 mA
SuperBus 2000 ATP 2600 alphanumeric
touchpad
22 ga.: 300 ft.
18 ga.: 750 ft.
30 mA
165 mA
SuperBus 2000 fixed display touchpad
22 ga.: 300 ft.
18 ga.: 700 ft.
11 mA
65 mA
SuperBus 2000 FTP 1000 fixed display
touchpad
22 ga.: 300 ft.
18 ga.: 700 ft.
12 mA
75 mA
SuperBus 2000 RF transceiver
22 ga.: 1,000
ft.
18 ga.: 2,500
ft.
45 mA
55 mA
SuperBus 2000 phone interface/voice module
22 ga.: 40 ft.
18 ga.: 120 ft.
25 mA
600 mA
SuperBus 2000 voice-only module
22 ga.: 40 ft.
18 ga.: 120 ft.
20 mA
300 mA (jumper)
600 mA (no
jumper)
SuperBus 2000 2 amp power supply
No load
No load
4 input/2 output SnapCard
N/A
20 mA
185 mA*
8Z hardwired zone expander SnapCard
N/A
38 mA
230 mA*
4 output SnapCard
N/A
1 mA
130 mA*
SuperBus 2000 8Z input module
22 ga.: 1,800
ft.
18 ga.: 4,000
ft.
18 mA
35 mA
SuperBus 2000 4-relay output module
22 ga.: 350 ft.
18 ga.: 900 ft.
12 mA
180 mA