Installation Manual Instruction Manual

Appendix B: Reference tables
144 Concord 4 Installation Manual
Response number
Siren tracking
Trip delay
Response time
11
Yes [1]
No
Sustained [3]
12
Yes [1]
Yes [4]
Momentary
13
Yes [1]
Yes [4]
3 minutes [5]
14
Yes [1]
Yes [4]
Siren time [2]
15
Yes [1]
Yes [4]
Sustained [3]
[1] If an event does not trigger sirens, siren tracking response numbers activate without turning on
the output. If sirens are triggered by another event, the output pulses to match the siren. If the
siren cadence changes (from police to fire, for example), outputs set up for siren tracking change
to match the siren and all pulsing outputs pulse to one common cadence.
[2] If an event does not trigger sirens, siren time response times activate outputs only if sirens are
active for another reason.
[3] If an alarm event does not necessarily require disarming (no activity, closing report, etc.),
outputs set up for a sustained response time remain activated until the next arming level change.
[4] If an event occurs that activates an output set up for trip delay, the delay and output activation
can be canceled by trigger event restoral.
[5] Activated outputs set up for a 3-minute response time remain active for the entire three
minutes. To deactivate the output before the 3-minute time expires, you must enter program
mode or remove panel power. Activated outputs set up for a momentary or 3-minute response
time restart if the same trigger event occurs again.
Note: The mechanical lifetime of the relay may be exceeded if an output is set up
for a siren tracking response and a pulsing siren (auxiliary or fire) is active for
long periods. A SnapCard relay output’s lifetime expectancy is about 350 total
pulsing hours.
Note: The trip delay is factory set for 30 seconds and cannot be changed.