Chapter 3: Programming
62 Concord 4 Installation Manual
Shortcut: 06007
Default: Off
When turned off, no report is sent.
Zone restorals
Shortcut: 06008
Default: Off
When this setting is on, the panel reports a restoral to the central
monitoring station for wireless or hardwire zones in alarm before the
alarm is canceled.
Hardwired smoke detectors connected to panel or SnapCard
hardwired zones do not send restorals.
Two-trip
Shortcut: 06009
Default: Off
This setting works with the Alarm verify setting (see Alarm verify in
Reporting - partition 1 to 6 settings on page 64. If Alarm verify is on,
the panel waits for a second sensor trip before sending an alarm.
If two-trip is on and a second sensor trip does not occur within 4
minutes, the panel sends an error report to the central monitoring
station.
Touchpad panic
report format
Shortcut: 06010
Default: Off
This setting determines how the panel formats touchpad panic alarm
reports to the central station. When this feature is turned on, touchpad
panic alarms report using the following three-digit codes:
Auxiliary597
Police—598
Fire—599
When turned off, touchpad panic alarms report using a three-digit
code from 500 to 515, with the last two digits identifying the touchpad
device number.
AC failure
Shortcut: 06011
Default: Off
When this setting is on, the panel reports to the central station at a
random time between 15 and 45 minutes after AC power to the panel
is lost. Making the report random helps prevent systems in an area
affected by a power outage from trying to report at the same time.
If this feature and the auxiliary power failure feature are both on, the
panel also monitors for and reports an AC failure for the SuperBus
2000 2-amp power supply.
Receiver failure
Shortcut: 06012
Default: Off
When this setting is on, the panel reports a receiver failure under the
following conditions:
No wireless sensor signals have been received for two hours.
The receiver is being jammed with a constant signal.