Installation Manual Instruction Manual

Chapter 3: Programming
78 Concord 4 Installation Manual
Onboard options menu
The Onboard options menu includes input, output programming, and output text
settings.
Onboard options - inputs settings
Smoke verify
Shortcut: 1100
Default: Off
This setting control the number of sensor group 26 (fire) zone trips
needed to report a fire alarm.
When turned off, hardwire and wireless smoke alarms are reported
immediately.
When turned on:
Hardwire smoke sensors. Onboard or SnapCard zones learned into
group 26 must be in alarm for at least 3 seconds or tripped twice within
5 minutes before activating system sirens and reporting to a central
station (or pager).
Wireless smoke sensors. The firest trip of a group 26 RF sensor will
cause a local fire alarm. The second trip of any group 26 zone within the
siren timeout will cause that fire alarm to be reported to the central
station.
Note: RF smoke detectors repeat the alarm transmission every 60
seconds as long as they are detecting smoke. This repeated
transmission will serve as the second zone trip, causing the alarm to be
reported.
Note: For California State Fire Marshall Listed installations, this feature
must be off.
Two-wire smoke
Shortcut: 1101
Default: Off
This setting determines how onboard hardwired zone 8 is configured.
When this setting is on, zone 8 will be configured for two-wire smoke
detectors. When off, it will be configured for a normal hardwire input.