Installation Manual

Electronic
7-Day Time Switch
Time Switch
Input Voltage: 120/208/240/277 VAC, 50/60 Hz•
Power Consumption: 6.0 watts max.•
ContactConguration:SPST(ET1705C),DPST(ET1725C),and•
SPDT(ET8115C).Seewiringdiagramsonnextpage.
Switch Ratings—ET1705C, ET1725C (per pole)
30AInductive/Resistive:24/120/208/240/277VAC,60Hz•
20A Ballast: 120-277 VAC, 60 Hz•
20AResistive:28VDC•
5ATungsten:120/240VAC,60Hz•
1 HP: 120 VAC, 60 Hz•
2 HP: 240 VAC, 60 Hz•
Switch Ratings—ET1715C (NO/NC) Normally Open/Normally Closed Contact
20A/10AInductive/Resistive:120/208/240/277VAC,60Hz•
20A/10AResistive:28VDC•
6A/3A Ballast: 120-277 VAC, 60 Hz•
5A/3A:120/240VACTungsten•
1 HP / ¼ HP: 120 VAC, 60 Hz•
2 HP / ½ HP: 240 VAC, 60 Hz•
Set Points (Events)—EachloadoutputoftheTimeSwitchcansupportup
to14timedONand14timedOFFeventsperday.
Battery-Powered Clock Operation—2yearsminimum(uses2AAA
industrialgradealkalinebatteries,supplied)
Minimum ON or OFF time—1 minute
Maximum ON or OFF time—6days,23hours,59minutes
Shipping Weight—2.5lb.(1.1kg)
Enclosures—Threeenclosureoptionsareavailable.
ET17x5C–NEMA1indoormetalenclosure•
ET17x5CR–NEMA3Rindoor/outdoorlockablemetalenclosure•
ET17x5CPD82–NEMA3Rindoor/outdoorlockableimpactresis-•
tantpolycarbonateenclosurewithclearcover
Knockouts—Combination1/2-3/4inchsize,1onbackandeachside,
2onbottom
Wire Size—AWG#10through#18
Installation and User Instructions
MODEL ET1700 Series
TheIntermaticET1700SeriesElectronic7-DayTimeSwitchauto-
maticallyswitchesloadstoapresetweeklyschedulewithto-the-
minuteaccuracy.
Theindependent7-dayprogrammingprovidescompleteexibility
forapplicationswhereloadswitchingdifferseachdayoftheweek.
UsetheET1700seriesasanON/OFFtimerinapplicationsrequir-
ing7-dayloadcontrolsuchaslighting,airconditioningsystems,
pumps,etc.EachloadoutputoftheTimeSwitchcansupportupto
14timedONand14timedOFFeventsperday.Theprogramcan
beoverriddenbypushingtheON/OFFloadoverridebutton(s).
TheET1700SeriesTimeSwitchisdesignedtodirectlyswitchtung-
stenorballastloadsuptoitsrating,andinductiveorresistiveloads
up to 30A at 120, 208, 240, or 277 VAC.
Specifications
With Battery
Carryover
Description
WARNING: Disconnect the
power to the Time Switch
and the loads before instal-
lation.
Removethemecha-1.
nismfromthecaseby
depressingthecatchat
thetopofthecaseand
pullingout,asshown.
CAUTION: Do not
touch circuit board
components since
static discharge could damage the microprocessor.
Setvoltageselectorfordesiredinputvoltage.2.
Thetimerisshippedwithvoltagesetfor120
VAC.Tooperateat208,240or277VAC,move
theselectorswitchtothedesiredsettingas
markedonthecircuitboard.SeelocationA in
Rear Viewaboveanddetailattheright.
ThetimerisshippedwithDST(DaylightSav-3.
ingTime)enabled.TodisableDST,insertajumperatlocation
markedDST.SeelocationB in Rear Viewabove
anddetailattheright.
ET1725C ONLY4. —Decidewhetheryouwant
tocontrolmultipleloadssimultaneously(SIM),
independently(IND),orwitha2-secondpulse
(PUL)(e.g.,forusewithmechanicallyheldcon-
tactorsorbellringingapplications),andmakesurethejumperis
positionedaccordingly.SeelocationB in Rear Viewaboveand
detailattheright.(TheunitisshippedwiththeloadssetforIND.)
Installation Instructions
Slide down
to remove
battery case
Snap out catch
Tilt top forward
Front View
Rear View
B
A
Electrical shock hazard. To avoid fire, shock, or death, disconnect all •
power before installing or servicing time switch or connected loads.
Follow local electrical and safety codes, National Electric Code (NEC) •
and Occupational Safety and Health Act Codes (OSHA).
If the power disconnect point is out of sight, lock it in the OFF position •
and tag it to prevent unexpected application of power.
This time switch must be grounded.•
Do not exceed maximum current carrying capacity.•
Always replace the plastic insulator covering the terminal before •
powering ON.
WARNING–Risk of Fire or Electric Shock

Summary of content (3 pages)