Use and Care Guide

www.intermatic.com
Surge Protection
Diagrams
IG Series
Specification
The Surge Protective Device shall be listed by CSA to ANSI/UL 1449 3rd Edition for Type 1 and Type 2 locations. The
Surge Protective Device shall provide protection between each phase conductor and ground. The Maximum
Continuous Operating Voltage (MCOV) shall be a minimum of ____volts AC between phase and ground. When subjected
to the ANSI / UL 1449 3rd Edition 20kA test impulses, the Voltage Protection Rating shall be no greater than 700 volts
Line to Neutral, 1200 volts Line to Line. The Surge Protective Device shall employ Large MOV technology and provide
individual component thermal protection and monitoring, utilizing a green LED status indicator. The failure of a
single component turns the LED OFF. The IG1240RC3 rainproof housing shall be constructed of UV resistant
polycarbonate, or material of equal strength and UV resistance, and tested to UL Type 3R standards for outdoor use. A
one half inch polycarbonate threaded nipple and metal locknut shall be provided. Leads shall be 12 gauge minimum and
24 inches in length. The IG3240RC3 rainproof housing shall be formed of 18 gauge powder coated sheet metal tested
to UL Type 3R standards for outdoor use. (A one half inch threaded nipple and metal locknut shall be provided). Leads
shall be 12 gauge minimum and 24 inches in length. The Surge Protective Device shall carry a 5-year product warranty
(IG3240RC3 10-year warranty) and also carry a $__________ connected equipment coverage warranty for ve years on
appliances and electronics.
Line
Line
Neutral
Ground
GREEN
WHITE
BLACK
BLACK
120
VAC
120 VAC
120 VAC
240 VAC
120 VAC
Model
Number
Service Voltage Phase
Leads#/
Length
Gauge
Nominal
Discharge
Current
SSCR MCOV
VPR
L-N, L-L, L-G, N-G
SPD Type 2 2
IG1300-2T-1C3 120/240 VAC 2 4/24" 12 20 kA 50 kA
150 L-N, N-G
300 L-L, L-G
700 L-N, 1200 L-L,
1200 L-G, 700 N-G
IG1300-4T-2C3 120/240 VAC 2 4/24" 12 20 kA 50 kA
150 L-N, N-G
300 L-L, L-G
700 L-N, 1200 L-L,
1200 L-G, 700 N-G
SPD Type 1 or 2
IG1240RC3 120/240 VAC 2 4/30" 12 20 kA 50 kA
150 L-N, N-G
300 L-L, L-G
700 L-N, 1200 L-L,
1200 L-G, 700 N-G
IG3240RC3 120/240 VAC 2 4/30" 12 20 kA 50 kA
150 L-N, N-G
300 L-L, L-G
700 L-N, 1200 L-L,
1200 L-G, 700 N-G
SCCR = Short Circuit Current Rating
MCOV = Maximum Continuous Operation Voltage
VPR = Voltage Protection Rating
SPD Type 1= applications include outdoor installations before service entrances and
utility meter cabinets
SPD Type 2= applications include installatons after service entrances
Main Breaker
2-Pole, 20A circuit
breaker shown
A=Black (Line)
B=Black (Line)
C=Neutral (White)
D= Green (Ground)
A=Black (Line)
B=Black (Line)
C=Neutral (White)
D=Green (Ground)