Instructions

Intesis
TM
BACnet Server DALI User Manual r1.1 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
106 / 172
6.3.70 Uyxx_Fast Fade Time
Present_value takes value 0 to 27, encoded in the following way:
0: <25 ms
1: 25 ms
2: 50 ms
3: 75 ms
4: 100 ms
5: 125 ms
6: 150 ms
7: 175 ms
8: 200 ms
9: 225 ms
10: 250 ms
11: 275 ms
12: 300 ms
13: 325 ms
14: 350 ms
15: 375 ms
16: 400 ms
17: 425 ms
18: 450 ms
19: 475 ms
20: 500 ms
21: 525 ms
22: 550 ms
23: 575 ms
24: 600 ms
25: 625 ms
26: 650 ms
27: 675 ms
Property Identifier
Property Datatype
Value
ASHRAE
IBOX
Object_Identifier
BACnetObjectIdentifier
(Analog Input, 7000* y + (100 * xx) + 43)
y stands for line number (0 or 1)
xx stands for short address, 0 to 63
R
R
Object_Name
CharacterString
Uyxx_Fast Fade Time
y stands for line (A or B)
xx stands for short address, 0 to 63
R
R
Object_Type
BACnetObjectType
ANALOG_INPUT (0)
R
R
Present_Value
REAL
x
R
R
Description
CharacterString
-
O
-
Device_Type
CharacterString
-
O
-
Status_Flags
BACnetStatusFlags
{FALSE, FALSE/TRUE, FALSE, FALSE}
R
R
Event_State
BACnetEventState
STATE_NORMAL (0)
R
R
Reliability
BACnetReliability
NO_FAULT_DETECTED (0),
UNRELIABLE_OTHER (7)
O
R
Out_Of_Service
BOOLEAN
FALSE
R
R
Update_Interval
Unsigned
-
O
-
Units
BACnetEngineeringUnits
no_units (95)
R
R
Min_Pres_Value
REAL
-
O
-