6.3.76 Iyxx_Occupancy InputValue / Iyxx_Light InputValue
Depending on the sensor instance configured this object can be an Analg Input for Light intances or Multistate input
for Occupancy intances. See below objects and properties for each type:
Property Identifier
Property Datatype
Value
ASHRAE
IBOX
Object_Identifier
BACnetObjectIdentifier
(Analog Input, 14000 + (640*y) + (10*xx) + z)
y stands for line number (0 or 1)
xx stands for sensor index, 0 to 63
z stands for instance index, 0 to 9
R
R
Object_Name
CharacterString
Iyxx_Light InputValue
y stands for line (A or B)
xx stands for sensor index, 0 to 63
R
R
Object_Type
BACnetObjectType
ANALOG_INPUT (0)
R
R
Present_Value
REAL
x
R
R
Description
CharacterString
-
O
-
Device_Type
CharacterString
-
O
-
Status_Flags
BACnetStatusFlags
{FALSE, FALSE/TRUE, FALSE, FALSE}
R
R
Event_State
BACnetEventState
STATE_NORMAL (0)
R
R
Reliability
BACnetReliability
NO_FAULT_DETECTED (0),
UNRELIABLE_OTHER (7)
O
R
Out_Of_Service
BOOLEAN
FALSE
R
R
Update_Interval
Unsigned
-
O
-
Units
BACnetEngineeringUnits
luxes (37)
R
R
Min_Pres_Value
REAL
-
O
-
Max_Pres_Value
REAL
-
O
-
Resolution
REAL
-
O
-
COV_Increment
REAL
0
O
R
Time_Delay
Unsigned
-
O
R*
Notification_Class
Unsigned
-
O
R*
High_Limit
REAL
-
O
R*
Low_Limit
REAL
-
O
R*
Deadband
REAL
-
O
R*
Limit_Enable
BACnetLimitEnable
-
O
R*
Event_Enable
BACnetEventTransitionBits
-
O
R*
Acked_Transitions
BACnetEventTransitionBits
-
O
R*
Notify_Type
BACnetNotifyType
-
O
R*
Event_Time_Stamps
BACnetArray[N] of
BACnetTimeStamp
-
O
R*
Profile_Name
CharacterString
-
O
-
* Only available when specific object has a Notification Class configured