Instructions
Intesis
TM
BACnet Server – DALI User Manual r1.1 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
125 / 172
6.3.85 Gyxx_Set Fade Time
Present_value takes value 0 to 15, with meaning:
• 0: Extended fade time (not supported)
• 1: 0,7s
• 2: 1s
• 3: 1,4s
• 4: 2s
• 5: 2,8s
• 6: 4s
• 7: 5,7s
• 8: 8s
• 9: 11,3s
• 10: 16s
• 11: 22,6s
• 12: 32s
• 13: 45,3s
• 14: 64s
• 15: 90,5s
Property Identifier
Property Datatype
Value
ASHRAE
IBOX
Object_Identifier
BACnetObjectIdentifier
(Analog Output, 7000* y + (20 * xx) + 6404)
y stands for line number (0 or 1)
xx stands for group number, 0 to 15
R
R
Object_Name
CharacterString
Gyxx_Set Fade Time
y stands for line (A or B)
xx stands for group number, 0 to 15
R
R
Object_Type
BACnetObjectType
ANALOG_OUTPUT (1)
R
R
Present_Value
REAL
x
W
W
Description
CharacterString
-
O
-
Device_Type
CharacterString
-
O
-
Status_Flags
BACnetStatusFlags
{FALSE, FALSE, FALSE, FALSE}
R
R
Event_State
BACnetEventState
STATE_NORMAL (0)
R
R
Reliability
BACnetReliability
NO_FAULT_DETECTED (0)
O
R
Out_Of_Service
BOOLEAN
FALSE
R
R
Update_Interval
Unsigned
-
O
-
Units
BACnetEngineeringUnits
no_units (95)
R
R
Min_Pres_Value
REAL
-
O
-
Max_Pres_Value
REAL
-
O
-
Resolution
REAL
-
O
-
COV_Increment
REAL
0
O
R
Priority_Array
BACnetPriorityArray
BACnetPriorityArray
R
R
Relinquish_Default
Unsigned
Configurable through BACnet and Config Tool
R
R
Time_Delay
Unsigned
-
O
R*
Notification_Class
Unsigned
-
O
R*