Instructions

Intesis
TM
BACnet Server DALI User Manual r1.1 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
149 / 172
7 Connections
Find below information regarding the Intesis connections available.
Power Supply
Must use NEC Class 2 or Limited Power Source (LPS) and
SELV rated power supply.
Respect polarity applied of terminals (+) and (-). Be sure the
voltage applied is within the range admitted (check table in
section 10). The power supply can be connected to earth but
only through the negative terminal, never through the positive
terminal.
Ethernet / BACnet IP
Connect the cable coming from the IP network to the
connector ETH of the gateway. Use an Ethernet CAT5 cable.
If communicating through the LAN of the building, contact the
network administrator and make sure traffic on the port used
is allowed through all the LAN path (check the gateway user
manual for more information). With factory settings, after
powering up the gateway, DHCP will be enabled for 30
seconds. After that time, if no IP is provided by a DHCP server,
the default IP 192.168.100.246 will be set.
PortA / DALI #0
Connect the DALI bus to connectors A4 (+), A3 (-) of gateway’s
PortA. Intesis provides 16VDC (+/-2%) DALI voltage to the
bus.
PortB / BACnet MSTP (INBACDAL0640200 / 1 DALI channel)
Connect the EIA485 bus to connectors B1 (B+), B2 (A-) and B3 (SNGD) of gateway’s PortB. Respect the polarity.
Remember the characteristics of the standard EIA485 bus: maximum distance of 1200 meters, maximum 32 devices
connected to the bus, and in each end of the bus it must be a termination resistor of 120 Ω. The gateway has an
internal bus biasing circuit that incorporates the termination resistor. If you install the gateway in one of the ends of
the bus, then do not install an additional termination resistor in that end.
PortB / DALI #1 (INBACDAL1280200 / 2 DALI channels)
Connect the DALI bus to connectors B2 (+), B1 (-) of gateway’s PortA. Intesis provides 16VDC (+/-2%) DALI voltage
to the bus.
Console Port
Connect a mini-type B USB cable from your computer to the gateway to allow communication between the
Configuration Software and the gateway. Remember that Ethernet connection is also allowed.
USB
Connect a USB storage device (not a HDD) if required. Check port caratheristics on section 10.
Ensure proper space for all connectors when mounted (see section 11).