Instructions
Intesis
TM
BACnet Server – DALI User Manual r1.1 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
152 / 172
8 Status LEDs and push buttons
LED
Colour
Indication
Run
Off
No power
Green
Device powered and working.
Error
Off
No error
Red
Error
Port A (Tx/Rx) – DALI #0
Off
There is no activity on this port.
Tx - Blinking green
Every data packet sent to UFO device it
blinks
Rx – Blinking yellow
Every data packet received from UFO
device it blinks
Port B (Tx/Rx) – DALI #1
(INBACDAL1280200 – 2 Channels)
Off
There is no activity on this port.
Tx - Blinking green
Every data packet sent to UFO device it
blinks
Rx – Blinking yellow
Every data packet received from UFO
device it blinks
Port B (Tx/Rx) – BACnet
(INBACDAL0640200 – 1 Channel)
Off
There is no activity on this port.
Tx - Blinking green
Every data packet sent to the network it
blinks
Rx – Blinking yellow
Every data packet received from an
slave device it blinks
Button A – DALI #0
Off / Red
Indicates status of last command sent
from the button (On-
RECALL_MAX_LEVEL, Off-OFF)
After 30 secs of not pushing the button,
the LED turns OFF and next time the
button is pushed it will begin with
RECALL_MAX_LEVEL
Button B – DALI #1
(INBACDAL1280200 – 2 Channels)
Off / Red
Indicates status of last command sent
from the button (On-
RECALL_MAX_LEVEL, Off-OFF)
After 30 secs of not pushing the button,
the LED turns OFF and next time the
button is pushed it will begin with
RECALL_MAX_LEVEL
Button B – BACnet
(INBACDAL0640200 – 1 Channel)
Off / Red
On when link is detected:
- BACnetIP: ethernet is up & running,
the IBOX got an IP
- BACnetMSTP: token passing is
detected