Figure A.4 Deleting devices
Finally, for all devices in configuration, you will need to define:
• For ballasts:
o ECG Name (optional): Name to ease its identification in the network
o Device type: It’s important that this field is suitably chosen and according to existing ballast in
the network (device type 0: Fluorescent Light, device type 1: Emergency Light, device type 6:
LED module or ‘Other’ (default) if none of the above matches the device type).
o Commitable ECG Parameters: This includes all preset values for the ballasts (min level, max
level, power on level, etc), as well as group assignation and scene configuration.
• For Input Devices (Sensors):
o Sensor Name (optional): Name to ease its identification in the network.
o Add required Instances: Each input device can include up to 32 different instance types (i.e.
instance type 4: Light sensor; instance type 3: Motion sensor; and so on…)
Scan and commissioning of devices
First you need to get MAPS connected to the Intesis device. To do so, go to ‘Connection’ tab of MAPS. There, select
appropriate connection mode (IP or USB). Select your device from the list of scanned devices (IP) or suitable COM
port (USB).