Instructions
Intesis
TM
BACnet Server – DALI User Manual r1.1 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
22 / 172
6.2.5 Input Device objects
Object-name
Description
Object-type
Object-instance
Iyxx_Occupancy InputValue /
Iyxx_Light InputValue
y stands for line (A or B)
xx stands for sensor index, 0 to 63
MI / AI
14000 + (640 * y) + (10 * xx) + z
y stands for line number (0 or 1)
xx stands for sensor index, 0 to 63
z stands for instance index, 0 to 9
6.2.6 Group objects
Object-name
Description
Object-type
Object-instance
Gyxx_Arc Power Level
y stands for line (A or B)
xx stands for sensor index, 0 to 63
AO
7000 * y + (20 * xx) + 6400
y stands for line number (0 or 1)
xx stands for group number, 0 to 15
Gyxx_Arc Power Off / On
BO
7000 * y + (20 * xx) + 6400
Gyxx_Step Up / Down
BO
7000 * y + (20 * xx) + 6401
Gyxx_Recall Min Level
BO
7000 * y + (20 * xx) + 6402
Gyxx_Recall Max Level
BO
7000 * y + (20 * xx) + 6403
Gyxx_Go to Scene
AO
7000 * y + (20 * xx) + 6401
Gyxx_Store Current Lvl as Scene
AO
7000 * y + (20 * xx) + 6402
Gyxx_Clear/Remove Scene
AO
7000 * y + (20 * xx) + 6403
Gyxx_Set Fade Time
AO
7000 * y + (20 * xx) + 6404
Gyxx_Set Fade Rate
AO
7000 * y + (20 * xx) + 6405
Gyxx_Set Min Level
AO
7000 * y + (20 * xx) + 6406
Gyxx_Set Max Level
AO
7000 * y + (20 * xx) + 6407
Gyxx_Set Power-on Level
AO
7000 * y + (20 * xx) + 6408
Gyxx_Set System-failure Level
AO
7000 * y + (20 * xx) + 6409
6.2.7 Broadcast objects
Object-name
Description
Object-type
Object-instance
By_Arc Power Level
y stands for line (A or B)
AO
7000 * y + 6800
y stands for line number (0 or 1)
By_Arc Power Off / On
BO
7000 * y + 6800
By_Step Up / Down
BO
7000 * y + 6801
By_Recall Min Level
BO
7000 * y + 6802
By_Recall Max Level
BO
7000 * y + 6803
By_Go to Scene
AO
7000 * y + 6801
By_Store Current Level as Scene
AO
7000 * y + 6802
By_Clear/Remove Scene
AO
7000 * y + 6803
By_Set Fade Time
AO
7000 * y + 6804
By_Set Fade Rate
AO
7000 * y + 6805
By_Set Min Level
AO
7000 * y + 6806
By_Set Max Level
AO
7000 * y + 6807
By_Set Power-on Level
AO
7000 * y + 6808
By_Set System-failure Level
AO
7000 * y + 6809