Instructions

Intesis
TM
BACnet Server DALI User Manual r1.1 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
38 / 172
6.3.12 Uyxx_Fade Time
Present_value takes values 0 to 15, where each value corresponds to:
0: Extended fade time (not supported)
1: 0,7s
2: 1s
3: 1,4s
4: 2s
5: 2,8s
6: 4s
7: 5,7s
8: 8s
9: 11,3s
10: 16s
11: 22,6s
12: 32s
13: 45,3s
14: 64s
15: 90,5s
Property Identifier
Property Datatype
Value
ASHRAE
IBOX
Object_Identifier
BACnetObjectIdentifier
(Analog Input, 7000* y + (100 * xx) + 8)
y stands for line number (0 or 1)
xx stands for short address, 0 to 63
R
R
Object_Name
CharacterString
Uyxx_Fade Time
y stands for line (A or B)
xx stands for short address, 0 to 63
R
R
Object_Type
BACnetObjectType
ANALOG_INPUT (0)
R
R
Present_Value
REAL
x
R
R
Description
CharacterString
-
O
-
Device_Type
CharacterString
-
O
-
Status_Flags
BACnetStatusFlags
{FALSE, FALSE/TRUE, FALSE, FALSE}
R
R
Event_State
BACnetEventState
STATE_NORMAL (0)
R
R
Reliability
BACnetReliability
NO_FAULT_DETECTED (0),
UNRELIABLE_OTHER (7)
O
R
Out_Of_Service
BOOLEAN
FALSE
R
R
Update_Interval
Unsigned
-
O
-
Units
BACnetEngineeringUnits
no_units (95)
R
R
Min_Pres_Value
REAL
-
O
-
Max_Pres_Value
REAL
-
O
-
Resolution
REAL
-
O
-
COV_Increment
REAL
0
O
R
Time_Delay
Unsigned
-
O
R*
Notification_Class
Unsigned
-
O
R*
High_Limit
REAL
-
O
R*
Low_Limit
REAL
-
O
R*