Instructions

Intesis
TM
BACnet Server DALI User Manual r1.1 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
45 / 172
6.3.17 Uyxx_Recall Min Level
Property Identifier
Property Datatype
Value
ASHRAE
IBOX
Object_Identifier
BACnetObjectIdentifier
(Binary Input, 7000* y + (100 * xx) + 2)
y stands for line number (0 or 1)
xx stands for short address, 0 to 63
R
R
Object_Name
CharacterString
Uyxx_Recall Min Level
y stands for line (A or B)
xx stands for short address, 0 to 63
R
R
Object_Type
BACnetObjectType
BINARY_INPUT (3)
R
R
Present_Value
BACnetBinaryPV
INACTIVE (0) / ACTIVE (1)
R
R
Description
CharacterString
-
O
-
Device_Type
CharacterString
-
O
-
Status_Flags
BACnetStatusFlags
{FALSE, FALSE/TRUE, FALSE, FALSE}
R
R
Event_State
BACnetEventState
STATE_NORMAL (0)
R
R
Reliability
BACnetReliability
NO_FAULT_DETECTED (0),
UNRELIABLE_OTHER (7)
O
R
Out_Of_Service
BOOLEAN
FALSE
R
R
Polarity
BACnetPolarity
NORMAL (0)
R
R
Inactive_Text
CharacterString
“”
O
R
Active_Text
CharacterString
Recall Min Level
O
R
Change_Of_State_Time
BACnetDatetime
-
O
R
Change_Of_State_Count
Unsigned
-
O
R
Time_Of_State_Count_Reset
BACnetDatetime
-
O
R
Elapsed_Active_Time
Unsigned
-
O
R
Time_Of_Active_Time_Reset
BACnetDatetime
-
O
R
Time_Delay
Unsigned
-
O
R*
Notification_Class
Unsigned
-
O
R*
Alarm_Value
BACnetBinaryPV
-
O
R*
Event_Enable
BACnetEventTransitionBits
-
O
R*
Acked_Transitions
BACnetEventTransitionBits
-
O
R*
Notify_Type
BACnetNotifyType
-
O
R*
Event_Time_Stamps
BACnetArray[N] of
BACnetTimeStamp
-
O
R*
Profile_Name
CharacterString
-
O
-
* Only available when specific object has a Notification Class configured