1 Description
Introduction
This document describes the integration of DALI-2 lighting ballasts and sensors with BACnet/IP or BACnet/MSTP
protocol compatible devices or systems using the gateway Intesis BACnet Server - DALI.
The aim of this integration is to monitor and control DALI-2 lighting ballasts and sensors (see section 2 for specific
DALI parts), remotely, for your Control Center using any BACnet based control system or device, as if it was a part
of the own BACnet system and vice-versa.
The gateway acts as a BACnet/IP Server or BACnet MSTP device in its BACnet interface, allowing other BACnet
devices to perform subscription (COV) requests and reads/writes to its internal points.
Up to 64 addresses for DALI lighting devices (ECGs), and another 64 addresses for Sensors can be fitted in a single
DALI channel, and therefore controlled and monitored from Intesis gateway. Depending on the version of the
gateway, 1 line (64 addresses for ECG and 64 addresses for Sensors) or 2 lines (128 addresses for ECG and 128
addresses for Sensors) are supported.
Version supporting 2 DALI channels does not have support for BACnet/MSTP it’s a BACnet/IP-only device.
Intesis needs to be configured using Intesis MAPS software configuration tool. In the software, BACnet and DALI
lighting device parameters must be configured and downloaded to the Intesis gateway.
This document assumes the user is familiar with BACnet and DALI technologies and technical terms.
Integration of DALI into BACnet IP / BACnet MSTP
control systems (product version supporting 1 DALI channel)
NOTE: Intesis is compatible with Ballasts and sensors implementeing DALI-2 standard
and certified under DiiA guidelines for testing and certification. Use only DALI-2 devices
having the DALI-2 logo with Intesis.
!