BACnet Server Digitally Addressable Lighting Interface (DALI-2) USER MANUAL Issue date: 06/2020 r1.
IntesisTM BACnet Server – DALI User Manual r1.1 EN Important User Information Disclaimer The information in this document is for informational purposes only. Please inform HMS Industrial Networks of any inaccuracies or omissions found in this document. HMS Industrial Networks disclaims any responsibility or liability for any errors that may appear in this document. HMS Industrial Networks reserves the right to modify its products in line with its policy of continuous product development.
IntesisTM BACnet Server – DALI User Manual r1.1 EN Gateway for the integration of DALI devices into BACnet MSTP or BACnet IP enabled monitoring and control systems. ORDER CODE INBACDAL0640200 INBACDAL1280200 © HMS Industrial Networks S.L.U - All rights reserved This information is subject to change without notice URL https://www.intesis.
IntesisTM BACnet Server – DALI User Manual r1.1 EN INDEX 1 Description ............................................................................................................................................... 7 Introduction ....................................................................................................................................... 7 Functionality ................................................................................................................................
IntesisTM BACnet Server – DALI 6.3.25 6.3.26 6.3.27 6.3.28 6.3.29 6.3.30 6.3.31 6.3.32 6.3.33 6.3.34 6.3.35 6.3.36 6.3.37 6.3.38 6.3.39 6.3.40 6.3.41 6.3.42 6.3.43 6.3.44 6.3.45 6.3.46 6.3.47 6.3.48 6.3.49 6.3.50 6.3.51 6.3.52 6.3.53 6.3.54 6.3.55 6.3.56 6.3.57 6.3.58 6.3.59 6.3.60 6.3.61 6.3.62 6.3.63 6.3.64 6.3.65 6.3.66 6.3.67 6.3.68 6.3.69 6.3.70 6.3.71 6.3.72 6.3.73 6.3.74 6.3.75 6.3.76 6.3.77 6.3.78 6.3.79 6.3.80 6.3.81 6.3.82 6.3.83 6.3.84 6.3.85 User Manual r1.1 EN Uyxx_Set Fade Rate .............
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.86 Gyxx_Set Fade Rate ............................................................................................................ 127 6.3.87 Gyxx_Set Min Level .............................................................................................................. 129 6.3.88 Gyxx_Set Max Level ............................................................................................................. 130 6.3.89 Gyxx_Set Power-on Level ........
IntesisTM BACnet Server – DALI User Manual r1.1 EN 1 Description Introduction This document describes the integration of DALI-2 lighting ballasts and sensors with BACnet/IP or BACnet/MSTP protocol compatible devices or systems using the gateway Intesis BACnet Server - DALI.
IntesisTM BACnet Server – DALI User Manual r1.1 EN Integration of DALI into BACnet IP / BACnet MSTP control systems (product version supporting 2 DALI channels) © HMS Industrial Networks S.L.U - All rights reserved This information is subject to change without notice URL https://www.intesis.
IntesisTM BACnet Server – DALI User Manual r1.1 EN Functionality IntesisTM continuously polls (reads) all the signals of the DALI ECGs and sensors to obtain updated readings for the points configured in it (the corresponding points list is explained later in this document). With every read, the new values received are updated in the gateway's memory and become available in the BACnet side.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 2 DALI Interface Intesis gateway and its DALI interface complies with the new DALI-2 (IEC62386) standard thanks to its DALI-2 certification. Intesis gateway enables the conection of up to 64 DALI/DALI-2 ECGs and 64 DALI-2 sensors.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 3 Protocol Implementation Conformance Statement BACnet Protocol Implementation Conformance Statement (PICS) Date: 2018-05-09 Vendor Name: HMS Industrial Networks S.L.U Product Name: INBACDAL---0200 Product Model Number: INBACDAL---0000 Application Software Version: 1.0 Firmware Revision: 1.0.0.0 BACnet Protocol Revision: 14 Product Description: DALI – BACnet MS/TP & BACnet IP Gateway Abstraction of DALI lighting ballasts registers as BACnet Objects.
IntesisTM BACnet Server – DALI User Manual r1.1 EN Device Address Binding: Is static device binding supported? (This is currently necessary for two-way communication with MS/TP slaves and certain other devices.) Yes No Networking Options: Router, Clause 6 - List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-MS/TP, etc.
IntesisTM BACnet Server – DALI User Manual r1.
IntesisTM BACnet Server – DALI User Manual r1.
IntesisTM BACnet Server – DALI User Manual r1.
IntesisTM BACnet Server – DALI User Manual r1.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6 Objects Supported Object Types The objects supported are shown in the table below. Object Type ID Analog-Input 0 Analog-Output 1 © HMS Industrial Networks S.L.
IntesisTM BACnet Server – DALI User Manual r1.
IntesisTM BACnet Server – DALI Trend-Log 20 Trend-Log-Multiple 27 © HMS Industrial Networks S.L.U - All rights reserved This information is subject to change without notice User Manual r1.1 EN URL https://www.intesis.
IntesisTM BACnet Server – DALI User Manual r1.1 EN Member objects 6.2.1 Gateway objects Object-name Device INBACDAL---0200* Description Object-type DALI to BACnet Gateway Object-instance 246* Device *Can be configured in MAPS *Can be configured in MAPS 6.2.
IntesisTM BACnet Server – DALI Uyxx_Emergency Battery Charge Uyxx_Next Function Test Uyxx_Next Duration Test Uyxx_Function Test Interval Uyxx_Duration Test Interval Uyxx_Test Execution Timeout Uyxx_Prolong Time Uyxx_Duration Test Result Uyxx_Lamp Total Operation Time Uyxx_Emergency Level Uyxx_Emergency Min Level Uyxx_Emergency Max Level Uyxx_Rated Duration Uyxx_Features Uyxx_Lamp Emergency Time Uyxx_Rest Uyxx_Inhibit Uyxx_Re-Light/Reset Inhibit Uyxx_Start Function Test Uyxx_Start Duration Test Uyxx_Stop Tes
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.2.5 Input Device objects Object-name Description Iyxx_Occupancy InputValue / Iyxx_Light InputValue Object-type MI / AI Object-instance 14000 + (640 * y) + (10 * xx) + z y stands for line number (0 or 1) xx stands for sensor index, 0 to 63 z stands for instance index, 0 to 9 y stands for line (A or B) xx stands for sensor index, 0 to 63 6.2.
IntesisTM BACnet Server – DALI User Manual r1.1 EN Objects and properties 6.3.1 INBACDAL---0000 (Device Object Type) Property Identifier Property Datatype Value Object_Identifier BACnetObjectIdentifier Object_Name ASHRAE IBOX (Device, 246000) R R CharacterString "INBACDAL---0000" R R Object_Type BACnetObjectType DEVICE (8) (Device Object Type) R R System_Status BACnetDeviceStatus OPERATIONAL (0) R R Vendor_Name CharacterString "HMS Industrial Networks S.L.
IntesisTM BACnet Server – DALI User Manual r1.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN Event_Time_Stamps BACnetArray[N] of BACnetTimeStamp - O R* Profile_Name CharacterString - O - * Only available when specific object has a Notification Class configured © HMS Industrial Networks S.L.U - All rights reserved This information is subject to change without notice URL https://www.intesis.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN Notify_Type BACnetNotifyType - O R* Event_Time_Stamps BACnetArray[N] of BACnetTimeStamp - O R* Profile_Name CharacterString - O - * Only available when specific object has a Notification Class configured © HMS Industrial Networks S.L.U - All rights reserved This information is subject to change without notice URL https://www.intesis.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN Notify_Type BACnetNotifyType - O R* Event_Time_Stamps BACnetArray[N] of BACnetTimeStamp - O R* Profile_Name CharacterString - O - * Only available when specific object has a Notification Class configured © HMS Industrial Networks S.L.U - All rights reserved This information is subject to change without notice URL https://www.intesis.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN Deadband REAL - O R* Limit_Enable BACnetLimitEnable - O R* Event_Enable BACnetEventTransitionBits - O R* Acked_Transitions BACnetEventTransitionBits O R* Notify_Type BACnetNotifyType - O R* Event_Time_Stamps BACnetArray[N] of BACnetTimeStamp - O R* Profile_Name CharacterString - O - - * Only available when specific object has a Notification Class configured © HMS Industrial Networks S.L.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN Limit_Enable BACnetLimitEnable - O R* Event_Enable BACnetEventTransitionBits - O R* Acked_Transitions BACnetEventTransitionBits O R* Notify_Type BACnetNotifyType - O R* Event_Time_Stamps BACnetArray[N] of BACnetTimeStamp - O R* Profile_Name CharacterString - O - - * Only available when specific object has a Notification Class configured © HMS Industrial Networks S.L.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN Event_Time_Stamps BACnetArray[N] of BACnetTimeStamp - O R* Profile_Name CharacterString - O - * Only available when specific object has a Notification Class configured © HMS Industrial Networks S.L.U - All rights reserved This information is subject to change without notice URL https://www.intesis.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN Event_Time_Stamps BACnetArray[N] of BACnetTimeStamp - O R* Profile_Name CharacterString - O - * Only available when specific object has a Notification Class configured © HMS Industrial Networks S.L.U - All rights reserved This information is subject to change without notice URL https://www.intesis.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN Event_Time_Stamps BACnetArray[N] of BACnetTimeStamp - O R* Profile_Name CharacterString - O - * Only available when specific object has a Notification Class configured © HMS Industrial Networks S.L.U - All rights reserved This information is subject to change without notice URL https://www.intesis.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.39 Uyxx_Prolong Time Present_value takes values 0 to 127.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.45 Uyxx_Rated Duration Present_value takes values 0 to 510 minutes.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN Event_Time_Stamps BACnetArray[N] of BACnetTimeStamp - O R* Profile_Name CharacterString - O - * Only available when specific object has a Notification Class configured © HMS Industrial Networks S.L.U - All rights reserved This information is subject to change without notice URL https://www.intesis.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.54 Uyxx_Reset Function T. Done Fl.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.55 Uyxx_Reset Duration T. Done Fl.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.57 Uyxx_Store T.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.58 Uyxx_Store Prolong Time Present_value takes value 0 to 127.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.59 Uyxx_Store Function T.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.60 Uyxx_Store Duration T.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI Profile_Name CharacterString User Manual r1.1 EN - O - * Only available when specific object has a Notification Class configured © HMS Industrial Networks S.L.U - All rights reserved This information is subject to change without notice URL https://www.intesis.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN Event_Time_Stamps BACnetArray[N] of BACnetTimeStamp - O R* Profile_Name CharacterString - O - * Only available when specific object has a Notification Class configured © HMS Industrial Networks S.L.U - All rights reserved This information is subject to change without notice URL https://www.intesis.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.73 Uyxx_Enable/Disable Curr. Prot.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.76 Iyxx_Occupancy InputValue / Iyxx_Light InputValue Depending on the sensor instance configured this object can be an Analg Input for Light intances or Multistate input for Occupancy intances.
IntesisTM BACnet Server – DALI Property Identifier Property Datatype Object_Identifier BACnetObjectIdentifier Object_Name CharacterString Object_Type User Manual r1.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 6.3.
IntesisTM BACnet Server – DALI User Manual r1.
IntesisTM BACnet Server – DALI 6.3.100 User Manual r1.
IntesisTM BACnet Server – DALI User Manual r1.1 EN Low_Limit REAL - O R* Deadband REAL - O R* Limit_Enable BACnetLimitEnable - O R* Event_Enable BACnetEventTransitionBits - O R* Acked_Transitions BACnetEventTransitionBits O R* Notify_Type BACnetNotifyType - O R* Event_Time_Stamps BACnetArray[N] of BACnetTimeStamp - O R* Profile_Name CharacterString - O - - * Only available when specific object has a Notification Class configured © HMS Industrial Networks S.L.
IntesisTM BACnet Server – DALI 6.3.101 User Manual r1.
IntesisTM BACnet Server – DALI 6.3.102 User Manual r1.
IntesisTM BACnet Server – DALI 6.3.103 User Manual r1.
IntesisTM BACnet Server – DALI 6.3.104 User Manual r1.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 7 Connections Find below information regarding the Intesis connections available. Power Supply Must use NEC Class 2 or Limited Power Source (LPS) and SELV rated power supply. Respect polarity applied of terminals (+) and (-). Be sure the voltage applied is within the range admitted (check table in section 10). The power supply can be connected to earth but only through the negative terminal, never through the positive terminal.
IntesisTM BACnet Server – DALI User Manual r1.1 EN Powering the device A power supply working with any of the voltage range allowed is needed (check section 10). Once connected the RUN led (Figure above) will turn on. WARNING! In order to avoid earth loops that can damage the gateway and/or any other equipment connected to it, we strongly recommend the use of DC power supplies, floating or with the negative terminal connected to earth.
IntesisTM BACnet Server – DALI User Manual r1.1 EN Having your DALI channel powered up, you can perform a quick DALI connectivity test by pressing Port A / Port B buttons: - When pressing Port A / Port B button, a broadcast command that will toggle the ballasts between 100% and 0% level will be sent. After 30s timeout of not pressing the button, ballasts will return back to its original level. DALI commands coming from BACnet will continue to be executed while doing this test.
IntesisTM BACnet Server – DALI User Manual r1.
IntesisTM BACnet Server – DALI Push button Button A – DALI #0 Button B – DALI #1 (INBACDAL1280200 – 2 Channels) Button B – BACnet (INBACDAL0640200 – 1 Channel) Functionality Sends to broadcast, alternatively: RECALL_MAX_LEVEL, OFF Sends to broadcast, alternatively: RECALL_MAX_LEVEL, OFF Sends to Broadcast I-Am message © HMS Industrial Networks S.L.U - All rights reserved This information is subject to change without notice User Manual r1.1 EN URL https://www.intesis.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 9 Set-up process and troubleshooting Pre-requisites It is necessary to have a BACnet IP or MSTP client device (BMS side device) operative and properly connected to the corresponding port of the gateway. It is also required to have a DALI installation connected to the gateway, in its respective DALI port/s.
IntesisTM BACnet Server – DALI User Manual r1.1 EN Figure 9.1 MAPS connection © HMS Industrial Networks S.L.U - All rights reserved This information is subject to change without notice URL https://www.intesis.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 9.2.3 Configuration tab Select the Configuration tab to configure the connection parameters. Three subsets of information are shown in this window: General (Gateway general parameters), BACnet Server (BACnet interface configuration) and DALI (DALI interface parameters). Figure 9.2 Intesis MAPS configuration tab 9.2.4 Signals All available objects, Object Instances, its corresponding DALI signal and other main parmaters are listed in the signals tab.
IntesisTM BACnet Server – DALI User Manual r1.1 EN Figure 9.3 Intesis MAPS Signals tab 9.2.5 Sending the configuration to Intesis When the configuration is finished, follow the steps to program the gateway. 1.- Click on Save button to save the project to the project folder on your hard disk (more information in Intesis MAPS User Manual). 2.- You will be prompted to generate the configuration file to be sent to the gateway. a.
IntesisTM BACnet Server – DALI User Manual r1.1 EN Figure 9.4 Intesis MAPS Receive/Send tab After any configuration change, do not forget to send the configuration file to the Intesis using button Send in section Receive / Send. 9.2.6 Diagnostic To help integrators in the commissioning tasks and troubleshooting, the Configuration Tool offers some specific tools and viewers. In order to start using the diagnostic tools, connection with the Gateway is required.
IntesisTM BACnet Server – DALI User Manual r1.1 EN Figure 9.5 Diagnostic More information about the Diagnostic section can be found in the Configuration Tool manual. © HMS Industrial Networks S.L.U - All rights reserved This information is subject to change without notice URL https://www.intesis.
IntesisTM BACnet Server – DALI User Manual r1.1 EN Set-up procedure 1. Install Intesis MAPS on your laptop, use the setup program supplied for this and follow the instructions given by the Installation wizard. 2. Install Intesis in the desired installation site. Installation can be on DIN rail or on a stable not vibrating surface (DIN rail mounted inside a metallic industrial cabinet connected to ground is recommended). 3.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 10 Electrical & Mechanical Features Enclosure Mounting Terminal Wiring (for power supply and low-voltage signals) Plastic, type PC (UL 94 V-0) Net dimensions (dxwxh): 90x88x56 mm Recommended space for installation (dxwxh): 130x100x100mm Color: Light Grey. RAL 7035 Wall. DIN rail EN60715 TH35. Per terminal: solid wires or stranded wires (twisted or with ferrule) 1 core: 0.5mm2… 2.5mm2 2 cores: 0.5mm2… 1.
IntesisTM BACnet Server – DALI User Manual r1.1 EN 11 Dimensions 56 mm (h) 88 mm (w) 90 mm (d) Recommended available space for its installation into a cabinet (wall or DIN rail mounting), with space enough for external connections 100 mm (h) 100 mm (w) © HMS Industrial Networks S.L.U - All rights reserved This information is subject to change without notice 130 mm (d) URL https://www.intesis.
IntesisTM BACnet Server – DALI User Manual r1.1 EN Annex A – Quick setup and commissioning of a DALI network This section provides a brief summary on commissioning a DALI channel using MAPS software tool.
IntesisTM BACnet Server – DALI User Manual r1.1 EN Create project You will need to create a new project, to do so, select ‘Create New project’ in MAPS start screen, and choose the appropriate template according to your device model (1 or 2 DALI channels): Figure A.1 New project creation Device declaration in project Once new project has been created, DALI devices can be added to the configured project, without the need of scanning them in bus.
IntesisTM BACnet Server – DALI User Manual r1.1 EN Figure A.2 Add new devices With suitable DALI channel selected, enter in ‘Add ECG(s)’/’Add Sensor(s)’ field the number of ECGs/Sensors to instantiate, and click button Add. Number of desired devices will appear: Figure A.3 Adding new sensors If too many devices have been instantiated, they can be deleted by selecting them, and pressing button ‘Delete ECG(s)’. Multiple selection is also possible. © HMS Industrial Networks S.L.
IntesisTM BACnet Server – DALI User Manual r1.1 EN Figure A.
IntesisTM BACnet Server – DALI User Manual r1.1 EN Figure A.5 Connecting MAPS to the Intesis Finally, click on button ‘Connect’ in order to establish connection. Bar at the bottom in MAPS main window will become green, switching from ‘Not Connected’ to ‘Connected’. Now go back to ‘Configuration’ tab of MAPS, and click on button ‘Commissioning’: Figure A.6 DALI commissioning button © HMS Industrial Networks S.L.
IntesisTM BACnet Server – DALI User Manual r1.1 EN Commissioning window will appear: Figure A.7 DALI commissioning window If having product version / template project supporting 2 DALI channels, channel to commission must be selected between ‘Port A’ (top of the device) or ‘Port B’ (bottom of the device). In case of version supporting single DALI channel, no selection is possible.
IntesisTM BACnet Server – DALI User Manual r1.1 EN Figure A.8 Starting DALI scan process Discovered devices will appear in the ‘DALI Network’ area, as soon as they are scanned. Network scan might take from several seconds up to a few minutes, depending on number of devices to scan. Field ‘Addr’ in list of ‘DALI Network’ will indicate ‘na’ if device has no associated short address (typical for new devices/factory settings) or a 0..
IntesisTM BACnet Server – DALI User Manual r1.1 EN B9F4AF 5CB6A9 Figure A.9 Example of scan results After scan is done, total number of found devices will be shown in ‘DALI Network:’ label. Note that type column will fill only if device has a short address assigned, if not, type cannot be read. Next step is associating a short address between 0 to 63 to each found ballast. To do so, following options are possible: 1.
IntesisTM BACnet Server – DALI User Manual r1.1 EN Figure A.10 Shot address association Once each device has a short address, ‘Wink’ functionality in “DALI Network’ window is available for each one. Wink functionality sets the ballast at maximum and minum level while it is actived, allowing to identify the physical location of the ballast in the installation. After identifying it in the installation, change in short address might be desired. After address association, devices can be added in config.
IntesisTM BACnet Server – DALI User Manual r1.1 EN Figure A.11 Functionality of ‘<<’ and ‘<-‘ buttons In Figure’s example, we’ll associate LED ballasts with short addres 0, 1 and 2 to existing ballasts (with ‘<-‘ button), and add ballast from short addresses 3 as new ballasts in the configuration (with ‘<<’ button).