BACnet Server M-Bus Meters USER MANUAL Issue date 11/2020 r1.
IntesisTM BACnet Server – M-Bus User Manual r1.6 eng Important User Information Disclaimer The information in this document is for informational purposes only. Please inform HMS Industrial Networks of any inaccuracies or omissions found in this document. HMS Industrial Networks disclaims any responsibility or liability for any errors that may appear in this document. HMS Industrial Networks reserves the right to modify its products in line with its policy of continuous product development.
IntesisTM BACnet Server – M-Bus User Manual r1.6 eng Gateway for the integration of M-Bus devices into BACnet MSTP or BACnet IP enabled monitoring and control systems. ORDER CODE INBACMEB0100000 INBACMEB0200000 INBACMEB0600000 INBACMEB1200000 LEGACY ORDER CODE IBBACMEB0100000 IBBACMEB0200000 IBBACMEB0600000 IBBACMEB1200000 © HMS Industrial Networks S.L.U - All rights reserved This information is subject to change without notice URL https://www.intesis.
IntesisTM BACnet Server – M-Bus User Manual r1.6 eng INDEX 1 Description ............................................................................................................................................... 5 Introduction ....................................................................................................................................... 5 Functionality ..............................................................................................................................
IntesisTM BACnet Server – M-Bus User Manual r1.6 eng Description Introduction This document describes the integration of M-Bus meters with BACnet ASHRAE 135 – 2001 Annex J - BACnet protocol compatible devices or systems using the gateway Intesis BACnet/IP Server - M-Bus. The aim of this integration is to make accessible M-Bus devices signals and resources from a BACnet based control system or device, as if it was a part of the own BACnet system and vice-versa.
IntesisTM BACnet Server – M-Bus User Manual r1.6 eng Functionality Intesis polls, either continuously or only when ordered from the BACnet side, the M-Bus devices to obtain updated readings for the points configured in it (the points corresponding to measures and states of the meters in the integration points list explained later in this document). With every read, the new values received are updated in the Intesis memory and become available in the BACnet side.
IntesisTM BACnet Server – M-Bus User Manual r1.6 eng Gateway’s capacity Intesis capacity is listed below: Element 10 version Type of BACnet devices 20 version 60 120 Notes version version IP / MSTP Communication with BACnet IP and MSTP. Number of BACnet Objects 250 500 1500 3000 Maximum number of points that can be defined in the virtual BACnet device inside the gateway.
IntesisTM BACnet Server – M-Bus User Manual r1.6 eng 2 Protocol Implementation Conformance Statement BACnet Protocol Implementation Conformance Statement (PICS) Date: 2017-09-18 Vendor Name: HMS Industrial Networks S.L.U Product Name: INBACMEB---0000 Product Model Number: INBACMEB---0000 Application Software Version: 1.0 Firmware Revision: 1.0.0.0 BACnet Protocol Revision: 12 Product Description: M-Bus – BACnet MS/TP & BACnet IP Gateway Abstraction of M-Bus slave device registers as BACnet Objects.
IntesisTM BACnet Server – M-Bus User Manual r1.6 eng Device Address Binding: Is static device binding supported? (This is currently necessary for two-way communication with MS/TP slaves and certain other devices.) Yes No Networking Options: Router, Clause 6 - List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-MS/TP, etc.
IntesisTM BACnet Server – M-Bus User Manual r1.
IntesisTM BACnet Server – M-Bus User Manual r1.
IntesisTM BACnet Server – M-Bus User Manual r1.
IntesisTM BACnet Server – M-Bus User Manual r1.
IntesisTM BACnet Server – M-Bus User Manual r1.6 eng 5 Objects Supported Object Types The objects supported are shown in the table below.
IntesisTM BACnet Server – M-Bus User Manual r1.6 eng Objects and properties 5.2.1 INBACMEB---0000 (Device Object Type) Property Identifier Property Datatype Value Object_Identifier BACnetObjectIdentifier Object_Name ASHRAE IBOX (Device, 246000) R R CharacterString "INBACMEB---0000" R R Object_Type BACnetObjectType DEVICE (8) (Device Object Type) R R System_Status BACnetDeviceStatus OPERATIONAL (0) R R Vendor_Name CharacterString "HMS Industrial Networks S.L.
IntesisTM BACnet Server – M-Bus User Manual r1.
IntesisTM BACnet Server – M-Bus User Manual r1.6 eng 5.2.
IntesisTM BACnet Server – M-Bus 5.2.3 User Manual r1.
IntesisTM BACnet Server – M-Bus User Manual r1.6 eng 5.2.
IntesisTM BACnet Server – M-Bus User Manual r1.6 eng 5.2.
IntesisTM BACnet Server – M-Bus User Manual r1.6 eng 5.2.
IntesisTM BACnet Server – M-Bus User Manual r1.6 eng 5.2.
IntesisTM BACnet Server – M-Bus User Manual r1.6 eng 5.2.
IntesisTM BACnet Server – M-Bus User Manual r1.6 eng 5.2.
IntesisTM BACnet Server – M-Bus User Manual r1.6 eng 5.2.
IntesisTM BACnet Server – M-Bus User Manual r1.6 eng 5.2.
IntesisTM BACnet Server – M-Bus User Manual r1.6 eng 5.2.
IntesisTM BACnet Server – M-Bus User Manual r1.6 eng 5.2.
IntesisTM BACnet Server – M-Bus User Manual r1.6 eng 5.2.
IntesisTM BACnet Server – M-Bus User Manual r1.6 eng 5.2.
IntesisTM BACnet Server – M-Bus User Manual r1.6 eng 6 Connections Find below information regarding the Intesis connections available. Power Supply Must use NEC Class 2 or Limited Power Source (LPS) and SELV rated power supply. Respect polarity applied of terminals (+) and (-). Be sure the voltage applied is within the range admitted (check table below). The power supply can be connected to earth but only through the negative terminal, never through the positive terminal.
IntesisTM BACnet Server – M-Bus User Manual r1.6 eng Powering the device A power supply working with any of the voltage range allowed is needed (check section 8). Once connected the RUN led (Figure above) will turn on. WARNING! In order to avoid earth loops that can damage the gateway and/or any other equipment connected to it, we strongly recommend the use of DC power supplies, floating or with the negative terminal connected to earth.
IntesisTM BACnet Server – M-Bus User Manual r1.6 eng Connection to M-Bus The gateway connects to the M-Bus system directly without requiring any external RS232 or RS485 to M-Bus level converter. Connect the M-Bus bus to connectors A3 (+) and A4 (-) of gateway’s PortA. Remember that the Intesis provides 36VDC M-Bus voltage to the bus, acting as a M-Bus level converter as well.
IntesisTM BACnet Server – M-Bus User Manual r1.6 eng 7 Set-up process and troubleshooting Pre-requisites It is necessary to have a M-Bus installation, device or interface operative and well connected to the corresponding M-Bus port of Intesis and a BACnet MSTP Master or BACnet IP client connected to their corresponding ports as well. Connectors, connection cables, PC to use the configuration tool and other auxiliary material, if needed, are not supplied by HMS Industrial Networks S.L.
IntesisTM BACnet Server – M-Bus User Manual r1.6 eng 7.2.3 Configuration tab Select the Configuration tab to configure the connection parameters. Three subsets of information are shown in this window: General (Gateway general parameters), BACnet Server (BACnet interface configuration) and M-Bus Master (M-Bus interface parameters). Figure 7.2 Intesis MAPS configuration tab 7.2.
IntesisTM BACnet Server – M-Bus User Manual r1.6 eng 7.2.5 Sending the configuration to Intesis When the configuration is finished, follow the next steps. 1.- Click on Save button to save the project to the project folder on your hard disk (more information in Intesis MAPS User Manual). 2.- You will be prompted to generate the configuration file to be sent to the gateway. a.- If Yes is selected, the file containing the configuration for the gateway will be generated and saved also into the project folder.
IntesisTM BACnet Server – M-Bus User Manual r1.6 eng Figure 7.5 Diagnostic More information about the Diagnostic section can be found in the Configuration Tool manual. © HMS Industrial Networks S.L.U - All rights reserved This information is subject to change without notice URL https://www.intesis.
IntesisTM BACnet Server – M-Bus User Manual r1.6 eng Set-up procedure 1. Install Intesis MAPS on your laptop, use the setup program supplied for this and follow the instructions given by the Installation wizard. 2. Install Intesis in the desired installation site. Installation can be on DIN rail or on a stable not vibrating surface (DIN rail mounted inside a metallic industrial cabinet connected to ground is recommended). 3.
IntesisTM BACnet Server – M-Bus User Manual r1.6 eng 8 Electrical & Mechanical Features Enclosure Mounting Terminal Wiring (for power supply and low-voltage signals) Plastic, type PC (UL 94 V-0) Net dimensions (dxwxh): 90x88x56 mm Recommended space for installation (dxwxh): 130x100x100mm Color: Light Grey. RAL 7035 Wall. DIN rail EN60715 TH35. Per terminal: solid wires or stranded wires (twisted or with ferrule) 1 core: 0.5mm2… 2.5mm2 2 cores: 0.5mm2… 1.
IntesisTM BACnet Server – M-Bus User Manual r1.6 eng 9 Dimensions 56 mm (h) 88 mm (w) 90 mm (d) Recommended available space for its installation into a cabinet (wall or DIN rail mounting), with space enough for external connections 100 mm (h) 100 mm (w) © HMS Industrial Networks S.L.U - All rights reserved This information is subject to change without notice 130 mm (d) URL https://www.intesis.