Instructions
Intesis
TM
BACnet Server – M-Bus User Manual r1.6 eng
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
16 / 40
Time_Synchronization_
Recipients
List of BACnetRecipient
-
O
-
Max_Master * **
Unsigned
127
R
W
Max_Info_Frames *
Unsigned
1
O
R
Device_Address_Binding
List of
BACnetAddressBinding
NULL (empty)
R
R
Database_Revision
Unsigned
0
R
R
Configuration_Files
BACnetArray[N] of
BACnetObjectIdentifier
-
O
-
Last_Restore_Time
BACnetTimeStamp
-
O
-
Backup_Failure_Timeout
Unsigned16
-
O
-
Active_COV_
Subscriptions
List of
BACnetCOVSubscription
List of BACnetCOVSubscription
O
R
Slave_Proxy_Enable
BACnetArray[N] of
BOOLEAN
-
O
-
Manual_Slave_Address_
Binding
List of
BACnetAddressBinding
-
O
-
Auto_Slave_Discovery
BACnetArray[N] of
BOOLEAN
-
O
-
Slave_Address_Binding
BACnetAddressBinding
-
O
-
Last_Restart_Reason
BACnetRestartReason
-
O
-
Time_Of_Device_Restart
BACnetTimeStamp
-
O
-
Restart_Notification_
Recipients
List of BACnetRecipient
-
O
-
UTC_Time_
Synchronization_
Recipients
List of BACnetRecipient
-
O
-
Time_Synchronization_
Interval
Unsigned
-
O
-
Align_Intervals
BOOLEAN
-
O
-
Interval_Offset
Unsigned
-
O
-
Profile_Name
CharacterString
-
O
-
* Only available when MSTP is used
** Configurable through the configuration tool.