5.2.14 Trend Log Object Type
Property Identifier
Property Datatype
Value
IBOX
Object_Identifier
BACnetObjectIdentifier
(Trend_Log, 20)
R
Object_Name
CharacterString
Configurable through BACnet and Config
Tool
R
Object_Type
BACnetObjectType
TREND_LOG (20)
R
Description
CharacterString
-
-
Enable
BOOLEAN
W
Start_Time
BACnetDateTime
W
Stop_Time
BACnetDateTime
W
Log_DeviceObjectProperty
BACnetDeviceObject
PropertyReference
-
Log_Interval
Unsigned
-
COV_Resubscription_Interval
Unsigned
-
Client_COV_Increment
BACnetClientCOV
-
Stop_When_Full
BOOLEAN
R
Buffer_Size
Unsigned
R
Log_Buffer
List of BACnetLogRecord
R
Record_Count
Unsigned
W
Total_Record_Count
Unsigned
R
Notification_Threshold
Unsigned
R*
Records_Since_Notification
Unsigned
R*
Last_Notify_Record
Unsigned
R*
Event_State
BACnetEventState
R
Notification_Class
Unsigned
R*
Event_Enable
BACnetEventTransitionBits
R*
Acked_Transitions
BACnetEventTransitionBits
R*
Notify_Type
BACnetNotifyType
R*
Event_Time_Stamps
BACnetARRAY[3] of
BACnetTimeStamp
R*
EventMessageTexts
BACnetARRAY[3] of
CharacterString
R*
Profile_Name
CharacterString
-
Logging_Type
BACnetLoggingType
R
Status_Flags
BACnetStatusFlags
R
* Only available when specific object has a Notification Class configured