Set-up procedure
1. Install Intesis MAPS on your laptop, use the setup program supplied for this and follow the instructions given by
the Installation wizard.
2. Install Intesis in the desired installation site. Installation can be on DIN rail or on a stable not vibrating surface
(DIN rail mounted inside a metallic industrial cabinet connected to ground is recommended).
3. If using BACnet IP, connect the communication cable coming from the BACnet IP network to the port marked as
Ethernet on Intesis (More details in section 6).
If using BACnet MSTP, connect the communication cables coming from the BACnet MSTP network to the port
marked as Port B on Intesis (More details in section 6).
4. Connect the M-Bus communication cable coming from the M-Bus network to the port marked as Port A on Intesis
(More details in section 6).
5. Power up Intesis. The supply voltage should be any of the voltage range allowed (check section 8). Take care of
the polarity of the supply voltage applied.
WARNING! In order to avoid earth loops that can damage Intesis and/or any other equipment connected to
it, we strongly recommend the use of DC power supplies, floating or with the negative terminal connected to
earth. Never use a DC power supply with the positive terminal connected to earth.
6. If you want to connect using IP, connect the Ethernet cable from the laptop PC to the port marked as Ethernet of
Intesis (More details in section 6).
If you want to connect using USB, connect the USB cable from the laptop PC to the port marked as Console of
Intesis (More details in section 6).
7. Open Intesis MAPS, create a new project selecting a copy of the one named INBACMEB---0000
8. Modify the configuration as desired, save it and download the configuration file to Intesis as explained in the
Intesis MAPS user manual.
9. Visit the Diagnostic section and check that there is communication activity, some TX frames and some other RX
frames. This means that the communication with the BACnet master device and M-Bus Slave devices is OK. In
case there is no communication activity between Intesis and the BACnet and/or M-Bus devices, check that those
are operative: check the baud rate, the communication cable used to connect all devices and any other
communication parameter.