Gateway’s capacity
Intesis capacity is listed below:
Element
20
version
60
version
120
version
Notes
Type of BACnet
devices
IP / MSTP
Communication with BACnet IP and MSTP.
Number of BACnet
Objects
500
1500
3000
Maximum number of points that can be
defined in the virtual BACnet device inside the
gateway.
Number of BACnet
Subscriptions (COV)
requests
1000
3000
6000
Maximum number of BACnet subscriptions
(COV) requests accepted by the gateway.
Type of M-Bus
devices
M-Bus EIA485 Slave devices
Those supporting M-Bus EN-1434-3
standard. Communication over RS485
Number of M-Bus
slave devices
10
20
60
120
Number of M-Bus slave devices supported
by the gateway.
Number of M-Bus
signals
250
500
1500
3000
Number of M-Bus signals (readings in the
meters) that can be read from Intesis.