Instructions
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL http://www.intesis.com
Rev.1.0
2 / 2
Enclosure
Plastic, type ABS (UL 94 V-0)
Net dimensions (dxwxh): 90x160x58 mm
Recommended space for installation (dxwxh): 130x160x100mm
Color: Light Grey. RAL 7035
Battery
Size: Coin 20mm x 3.2mm
Capacity: 3V / 225mAh
Type: Manganese Dioxide Lithium
Mounting
DIN rail EN60715 TH35.
Console
Port
Mini Type-B USB 2.0 compliant
1500VDC isolation
Terminal Wiring
(for power supply and
low-voltage signals)
Per terminal: solid wires or stranded wires (twisted or with
ferrule)
1 core: 0.5mm
2
… 2.5mm
2
2 cores: 0.5mm
2
… 1.5mm
2
3 cores: not permitted
USB port
Type-A USB 2.0 compliant
Only for USB flash storage device (USB pen
drive)
Power consumption limited to 150mA (HDD
connection not allowed)
Power
1 x Plug-in screw terminal block (3 poles)
Positive, Negative, Earth
24VDC +/-10% Max.: 580mA
Push Button
Button A: Check the user manual
Button B: Check the user manual
Operation
Temperature
0°C to +60°C
Ethernet
1 x Ethernet 10/100 Mbps RJ45
2 x Ethernet LED: port link and activity
Operational
Humidity
5 to 95%, no condensation
Port A
1 x Serial EIA485 (Plug-in screw terminal block 2 poles)
A, B
1 x Plug-in screw terminal block green (2 poles)
SGND (Reference ground or shield)
1500VDC isolation from other ports
Protection
IP20 (IEC60529)
Switch A
(SWA)
1 x DIP-Switch for PORT A configuration:
Position 1:
ON: 120 Ω termination active
Off: 120 Ω termination inactive
Position 2-3:
ON: Polarization active
Off: Polarization inactive
LED
Indicators
8 x On board LED indicators
1 x Error LED
1 x Power LED
2 x Port A TX/RX
2 x Port B TX/RX
1 x Button A indicator
1 x Button B indicator
PORT B
1 x EIA232 (SUB-D9 male connector)
Reserved for future use
1 x EIA485 port (Plug-in screw terminal block 3 poles)
Reserved for future use
Switch B
(SWB)
1 x DIP-Switch for serial EIA485 configuration:
Reserved for future use
PORT C
2 x Ethernet 10/100 Mbps RJ45
4 x Ethernet LED: 2 x port link and 2 x activity
CONNECTIONS
ELECTRICAL & MECHANICAL FEATURES
Power Supply
Must use NEC Class 2 or Limited Power Source (LPS) and SELV rated power
supply. Respect polarity applied of terminals (+) and (-). Be sure the voltage
applied is within the range admitted (check table below). The power supply
can be connected to earth but only through the negative terminal, never
through the positive terminal. Functional Earth shall be connected to the
installation Earth.
Ethernet / BACnet IP (UDP) / Console (UDP & TCP)
Connect the cable coming from the IP network to the connector ETH of the
gateway. Use an Ethernet CAT5 cable. If communicating through the LAN of
the building, contact the network administrator and make sure traffic on the
port used is allowed through all the LAN path (check the gateway user
manual for more information). With factory settings, after powering up the
gateway, DHCP will be enabled for 30 seconds. After that time, if no IP is
provided by a DHCP server, the default IP 192.168.100.246 will be set.
PortA / BACnet MS/TP
Connect the EIA485 bus to connectors A3 (+), A4 (-) and A1 or A2 (SNGD)
of gateway’s PortA. Respect the polarity. Remember the characteristics of
the standard EIA485 bus: maximum distance of 1200 meters, maximum 32
devices connected to the bus, and in each end of the bus it must be a
termination resistor of 120 Ω. The gateway has an internal bus biasing circuit
that incorporates the termination resistor. If you install the gateway in one of
the ends of the bus, then do not install an additional termination resistor in
that end.
PortB: Reserved for future use.
Port C / PROFINET
Connect the cables coming from the IP network to the PROFINET connectors
Console Port
Connect a mini-type B USB cable from your computer to the gateway to allow
communication between the Configuration Software and the gateway.
Remember that Ethernet connection is also allowed. Check the user manual
for more information. To be used only during the configuration stage.
USB
Only used by debugging services. It can connect a USB storage device (not
a HDD) if required. Check the user manual for more information.
Power Supply
Ethernet
BACnet IP
USB
storage
Console
Port
Port B
USB
EIA 232
B1 B2 B3
SW B
SW A
Ethernet Port
Port A
A1 A2
A3 A4
Power
zzzzz
Run / Error
Eth.Link/Spd
PortA TX/RX
PortB TX/RX
Button A
Button B
Console
- +
PROFINET
BACnet
MS/TP
Port C
This marking on the product, accessories, packaging or literature (manual) indicates that the product contains electronic
parts and they must be properly disposed of by following the instructions at https://intesis.com/weee-regulation
160 mm (w)
130 mm (d)
100 mm (h)