BACnet Server PROFINET IO Device USER MANUAL Issue date: 05/2020 r1.
IntesisTM BACnet Server – PROFINET User Manual r1.0 eng Important User Information Disclaimer The information in this document is for informational purposes only. Please inform HMS Industrial Networks of any inaccuracies or omissions found in this document. HMS Industrial Networks disclaims any responsibility or liability for any errors that may appear in this document. HMS Industrial Networks reserves the right to modify its products in line with its policy of continuous product development.
IntesisTM BACnet Server – PROFINET User Manual r1.0 eng Gateway to connect BACnet MSTP or BACnet IP installations with PROFINET networks. ORDER CODE INBACPRT1K20000 © HMS Industrial Networks S.L.U - All rights reserved This information is subject to change without notice URL https://www.intesis.
IntesisTM BACnet Server – PROFINET User Manual r1.0 eng INDEX 1. Description ............................................................................................................................................... 6 Introduction ....................................................................................................................................... 6 Functionality ..........................................................................................................................
IntesisTM BACnet Server – PROFINET User Manual r1.0 eng 9.2.5 Sending the configuration to Intesis ....................................................................................... 42 9.2.6 Diagnostic ............................................................................................................................... 42 Set-up procedure ............................................................................................................................ 44 10.
IntesisTM BACnet Server – PROFINET User Manual r1.0 eng 1. Description Introduction This document describes how to easily connect BACnet MS/TP or BACnet IP systems with PROFINET networks using the Intesis BACnet Server – PROFINET gateway. The aim of this integration is to share data between PROFINET IO Controllers and BACnet based control systems or devices, merging both systems into one.
IntesisTM BACnet Server – PROFINET User Manual r1.0 eng Functionality On the PROFINET side, the gateway acts as a PROFINET IO-Device, so after the start up process, the gateway presents its points as PROFINET IO data to exchange them cyclically or using acyclic Read/Write requests, according to their configuration. • Acyclic communication (Unscheduled, on demand communications).
IntesisTM BACnet Server – PROFINET User Manual r1.0 eng 2. Protocol Implementation Conformance Statement BACnet Protocol Implementation Conformance Statement (PICS) Date: 2018-05-16 Vendor Name: HMS Industrial Networks S.L.U Product Name: INBACPRT---0000 Product Model Number: INBACPRT---0000 Application Software Version: 1.0.0.0 Firmware Revision: 14.0.1.0 BACnet Protocol Revision: 14 Product Description: BACnet MS/TP & IP Server – PROFINET Gateway Abstraction of PROFINET data as BACnet Objects.
IntesisTM BACnet Server – PROFINET User Manual r1.0 eng Device Address Binding: Is static device binding supported? (This is currently necessary for two-way communication with MS/TP slaves and certain other devices.) Yes No Networking Options: Router, Clause 6 - List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-MS/TP, etc.
IntesisTM BACnet Server – PROFINET User Manual r1.0 eng 3.
IntesisTM BACnet Server – PROFINET User Manual r1.
IntesisTM BACnet Server – PROFINET User Manual r1.
IntesisTM BACnet Server – PROFINET User Manual r1.0 eng 4.
IntesisTM BACnet Server – PROFINET User Manual r1.0 eng 5. Objects Supported Object Types The objects supported are shown in the table below.
IntesisTM BACnet Server – PROFINET User Manual r1.0 eng Objects and properties 5.2.1 INBACPRT---0000 (Device Object Type) Property Identifier Property Datatype Value Object_Identifier BACnetObjectIdentifier Object_Name ASHRAE IBOX (Device, 246000) R R CharacterString "INBACPRT---0000" R R Object_Type BACnetObjectType DEVICE (8) (Device Object Type) R R System_Status BACnetDeviceStatus OPERATIONAL (0) R R Vendor_Name CharacterString "HMS Industrial Networks S.L.
IntesisTM BACnet Server – PROFINET User Manual r1.
IntesisTM BACnet Server – PROFINET User Manual r1.0 eng 5.2.
IntesisTM BACnet Server – PROFINET User Manual r1.0 eng 5.2.
IntesisTM BACnet Server – PROFINET User Manual r1.0 eng 5.2.
IntesisTM BACnet Server – PROFINET User Manual r1.0 eng 5.2.
IntesisTM BACnet Server – PROFINET User Manual r1.0 eng 5.2.
IntesisTM BACnet Server – PROFINET User Manual r1.0 eng 5.2.
IntesisTM BACnet Server – PROFINET User Manual r1.0 eng 5.2.
IntesisTM BACnet Server – PROFINET User Manual r1.0 eng 5.2.
IntesisTM BACnet Server – PROFINET User Manual r1.0 eng 5.2.
IntesisTM BACnet Server – PROFINET User Manual r1.0 eng 5.2.
IntesisTM BACnet Server – PROFINET User Manual r1.0 eng 5.2.
IntesisTM BACnet Server – PROFINET User Manual r1.0 eng 5.2.
IntesisTM BACnet Server – PROFINET User Manual r1.0 eng 5.2.
IntesisTM BACnet Server – PROFINET User Manual r1.0 eng 5.2.
IntesisTM BACnet Server – PROFINET User Manual r1.0 eng 6. PROFINET Module Secure HICP Intesis gateway supports the Secure HICP protocol used by the IPConfig tool for changing settings like IP address, Subnet mask, and enable/disable DHCP. This configuration interface can be used if configuration via the PROFINET configuration tool (via PROFINET DCP) is not possible or desired. By default, it is disabled but it can be enabled from Intesis MAPS tool.
IntesisTM BACnet Server – PROFINET User Manual r1.0 eng Web Server The built-in web server provides a flexible environment for end-user interaction and configuration purposes. By default, it is disabled, but it can be enabled from Intesis MAPS tool. The web server supports up to 20 concurrent connections and communicates through port 80.
IntesisTM BACnet Server – PROFINET User Manual r1.
IntesisTM BACnet Server – PROFINET User Manual r1.0 eng Media Redundancy Protocol (MRP) Media Redundancy Protocol (MRP) is a PROFINET specific ring protocol ensuring redundancy in the network, which can significantly decrease network downtime. It is a token-based ring protocol with a master-slave hierarchy. All the nodes in the PROFINET network part of the ring are connected using ring topology (that is, the last node is connected directly to the first node).
IntesisTM BACnet Server – PROFINET User Manual r1.0 eng Power Supply Must use NEC Class 2 or Limited Power Source (LPS) and SELV rated power supply. Respect polarity applied of terminals (+) and (-). Be sure the voltage applied is within the range admitted (check section 10). The power supply can be connected to earth but only through the negative terminal, never through the positive terminal.
IntesisTM BACnet Server – PROFINET User Manual r1.0 eng Connect a mini-type B USB cable from your computer to the gateway to allow communication between the Configuration Software and the gateway. Remember that Ethernet connection is also allowed. Check the user manual for more information. USB Connect a USB storage device (not a HDD) if required. Check the user manual for more information. Ensure proper space for all connectors when mounted (see section 11). © HMS Industrial Networks S.L.
IntesisTM BACnet Server – PROFINET User Manual r1.0 eng Powering the device A power supply working with any of the voltage range allowed is needed (check section 10). Once connected the RUN led (Figure above) will turn on. WARNING! In order to avoid earth loops that can damage the gateway and/or any other equipment connected to it, we strongly recommend: • The use of DC power supplies, floating or with the negative terminal connected to earth.
IntesisTM BACnet Server – PROFINET User Manual r1.0 eng Connection to PROFINET Connect the communication cables coming from previous and next device in the PROFINET network, using a line or ring topology. When ring topology is used, a device must take over the function of the ring manager (MRM). See section 6.4 Media Redundancy Protocol (MRP) for more details. If only one Ethernet connection is needed (e.g., last device in a line topology), either Port 1 or Port 2 can be used.
IntesisTM BACnet Server – PROFINET User Manual r1.0 eng 8. Status LEDs and push buttons LED Run Error Port A (Tx/Rx) – BACnet Colour Off Green Off Red Off Tx - Blinking green Rx – Blinking yellow Port B (Tx/Rx) – Expansion Module communication Off Tx - Blinking green Rx – Blinking yellow Indication No power Device powered and working. No error Error There is no activity on this port.
IntesisTM BACnet Server – PROFINET User Manual r1.0 eng 9. Set-up process and troubleshooting Pre-requisites It is necessary to have a BACnet IP client or MSTP device operative and well connected to the corresponding BACnet port of Intesis and a PROFINET IO Controller connected to their corresponding ports as well. Connectors, connection cables, PC to use the configuration tool and other auxiliary material, if needed, are not supplied by HMS Industrial Networks S.L.U for this standard integration.
IntesisTM BACnet Server – PROFINET User Manual r1.0 eng 9.2.3 Configuration tab Select the Configuration tab to configure the connection parameters. Three subsets of information are shown in this window: General (Gateway general parameters), BACnet Server (BACnet interface configuration) and PROFINET (interface parameters). Figure 9.2 Intesis MAPS configuration tab 9.2.
IntesisTM BACnet Server – PROFINET User Manual r1.0 eng 9.2.5 Sending the configuration to Intesis When the configuration is finished, follow the next steps. 1.- Click on Save button to save the project to the project folder on your hard disk (more information in Intesis MAPS User Manual). 2.- You will be prompted to generate the configuration file to be sent to the gateway. a.
IntesisTM BACnet Server – PROFINET User Manual r1.0 eng Figure 9.5 Diagnostic More information about the Diagnostic section can be found in the Configuraion Tool manual. © HMS Industrial Networks S.L.U - All rights reserved This information is subject to change without notice URL https://www.intesis.
IntesisTM BACnet Server – PROFINET User Manual r1.0 eng Set-up procedure 1. Install Intesis MAPS on your laptop, use the setup program supplied for this and follow the instructions given by the Installation wizard. 2. Install Intesis in the desired installation site. Installation can be on DIN rail or on a stable not vibrating surface (DIN rail mounted inside a metallic industrial cabinet connected to ground is recommended). 3.
IntesisTM BACnet Server – PROFINET 10. User Manual r1.0 eng Electrical & Mechanical Features Enclosure Plastic, type ABS (UL 94 V-0) Net dimensions (dxwxh): 90x160x58 mm Recommended space for installation (dxwxh): 130x160x100mm Color: Light Grey. RAL 7035 Battery Size: Coin 20mm x 3.2mm Capacity: 3V / 225mAh Type: Manganese Dioxide Lithium Mounting DIN rail EN60715 TH35. Console Port Mini Type-B USB 2.
IntesisTM BACnet Server – PROFINET 11. User Manual r1.0 eng Dimensions 58 mm (h) 160 mm (w) 90 mm (d) Recommended available space for its installation into a cabinet (wall or DIN rail mounting), with space enough for external connections 100 mm (h) 160 mm (w) © HMS Industrial Networks S.L.U - All rights reserved This information is subject to change without notice 130 mm (d) URL https://www.intesis.