Set-up procedure
1. Install Intesis MAPS on your laptop, use the setup program supplied for this and follow the instructions given by
the Installation wizard.
2. Install Intesis in the desired installation site. Installation can be on DIN rail or on a stable not vibrating surface
(DIN rail mounted inside a metallic industrial cabinet connected to ground is recommended).
3. If using BACnet IP, connect the communication cable coming from the BACnet IP network to the port marked as
Ethernet on Intesis (More details in section 6).
If using BACnet MSTP, connect the communication cables coming from the BACnet MSTP network to the port
marked as BACnet MSTP on Intesis (More details in section 6).
4. Power up Intesis. The supply voltage can be 9 to 24 Vdc. Take care of the polarity of the supply voltage applied.
WARNING! In order to avoid earth loops that can damage Intesis and/or any other equipment connected to
it, we strongly recommend the use of DC power supplies, floating or with the negative terminal connected to
earth. Never use a DC power supply with the positive terminal connected to earth.
5. If you want to connect using IP, connect the Ethernet cable from the laptop PC to the port marked as ETH of
Intesis (More details in section 6).
6. Open Intesis MAPS, create a new project selecting a copy of the one named INBACRTR0320000.
7. Modify the configuration as desired, save it and download the configuration file to Intesis as explained in the
Intesis MAPS user manual.
8. Visit the Diagnostic section and check that there is communication activity, some TX frames and some other RX
frames. This means that the communication with the two BACnet networks is OK. In case there is no
communication activity between Intesis and the BACnet devices, check that those are operative.