Figure 4.23 Parameter detail
All the parameters in this section are related with the Scene properties and communication
objects. A scene contains values of: On/Off, Mode, Fan speed, Vane position, Setpoint
Temperature and Remote Controller Disablement.
4.6.1 Enable use of scenes
This parameter shows/hides the scene configuration parameters and communication
objects.
o If set to “no” the scene parameters and communication objects will not be shown.
o If set to “yes” the scene parameters and communication objects will be shown. To
execute a scene through the byte-type object, a value from 0 to 4 has to be
sent, correponding each one to a different scene (i.e. 0 = Scene 1; 4 = Scene
5).
4.6.2 Enable use of bit objects for scene execution
This parameter shows/hides the Control_ Execute Scene bit-type communication objects.