o If set to “no” the communication objects will not be shown.
o If set to “yes” the communication objects will appear. To execute a scene by using
these objects, a “1” value has to be sent to the scene’s object we want to execute
(i.e. to execute scene 4, a “1” has to be sent to the Control_ Execute Scene 4
object).
4.6.3 Enable use of bit objects for storing scenes
This parameter shows/hides the Control_ Store Scene bit-type communication objects.
o If set to “no” the objects will not be shown.
o If set to “yes” the Control_ Store Scene objects for storing scenes will appear. To store
a scene by using these objects, a “1” value has to be sent to the scene’s object we want
to store (i.e. to store scene 4, a “1” has to be sent to the Control_ Store Scene 4
object).
4.7 Enable use of Window Contact function
This parameter shows/hides the Control_ Switch Off Timeout communication object which
lets Start/Stop a timeout to switch off the indoor unit.
o If set to “no” the object will not be shown.
o If set to “yes” the Control_ Switch Off Timeout object and new parameters will
appear. If a “1” value is sent to this object, and the indoor unit is already turned on,
the switch-off timeout will begin. If a “0” value is sent to this object, the switch-off
timeout will stop.