Once clicked on “Receive IR frame”, the following sequence will be executed:
1) The device will be prepared to receive the frame. During this period (up to 10s) no frame from IR
remote is expected and the device LED is OFF (sometimes a short red blink may be noticed).
2) Once the LED changes into steady white, the device is ready to receive the IR frame and a 30s
countdown will start. Kindly consider the following advices to do it in the proper way:
a. It is necessary to press ON/OFF once and wait for about 5s to let the device transmitting the
information to the PC. You can notice this transmission if the countdown freezes.
b. If ON/OFF button is pressed many times, the process may be enlarged till the user stops, as
the frame communication will not be the appropriate.
3) If the process finishes properly, the LED will switch OFF and a pop-up will be displayed with the
message "Frame Received". If the remote is available in the database, the remote will appear in
"Discovered RCF's" being highly recommended to use the "recomended remote" to match with the
integration needed.
In case the remote is not available in the database, you will get a pop-up warning with the following
message: "Frame could not be recognized". In this case, please, contact to our Support Team so that
they will inform you about the next steps.
Both manual or automatic remote configuration options need to press the button “Download IR parameters” to
download the current AC choice over INKNXUNI001I000. Please, make sure the option selected is the desired
one before starting this process as this process may last for some minutes. Refer to 4 ABOVE4 CONFIGURATION
AND SETUP for more information about IR parameter downloads available.
Other settings
5.1.3 Delay before sending initial “Read” telegrams
This parameter sets the delay before the interface will send READ telegrams for the group addresses associated
on its Control_ objects on bus recovery or application reset/start-up. All Control_ objects with both Transmit (T)
and Update (U) flags enabled will send READs and their values will be updated with the response when
received.
Valid values go from 10 to 60 seconds. This is to give time enough to other KNX devices on the bus to start-up
before sending the READs.
5.1.4 Scene to execute on bus recovery / startup
This parameter executes a selected scene on bus recovery or startup, only if the selected scene has an enabled
preset or values previously saved from KNX bus (see Scene Configuration dialog). You can select any of the 5
available scenes.