o If set to “no” the objects will not be shown.
o If set to “yes” the Control_ Vane Up-Down objects for each Position (1 to N) will appear. To activate a
Vane Position by using these objects, a “1” value has to be sent.
5.6.3 Enable use of bit-type Vane U-D objects (for Status)
This parameter shows/hides the bit-type Status_ Vane Up-Down objects.
o If set to “no” the objects will not be shown.
o If set to “yes” the Status_ Vane Up-Down objects for each Position (1 to N) will appear. When a Vane
Position is enabled, a 1” value is returned through its bit-type object.
5.6.4 Enable use of +/- obj for Vane Left-Right
This parameter shows/hides the Control_ Vane Left-Right +/- communication object which lets you change the
indoor unit vane position by using two different datapoint types.
o If set to “no” the object will not be shown.
o If set to “yes” the Control_ Vane Left-Right +/- object.
DPT type for +/- Vane Left-Right obj
This parameter lets choose between the datapoints 0-Up / 1-Down [DPT_1.008] and 0-Decrease / 1-
Increase [DPT_1.007] for the Control_ Vane Left-Right +/- object.
Rollover Vane at upper/lower limit
This parameter lets choose if roll-over will be enabled (“yes”) or disabled (“no”) for the Vane Up-Down
+/- object.
Pos. 3
Pos. 1
Pos. 2
Only if Roll-over is enabled
Only if Roll-over is enabled
Pos. 5
Pos. 4
SWING