This parameter lets choose between the datapoints 0-Up / 1-Down [DPT_1.008] and 0-Decrease / 1-
Increase [DPT_1.007] for the Control_ Setpoint Temp +/- object.
5.7.2 Set Point - Enable limits on Control_ Setpoint obj
This parameter enables to define temperature limits for the Control_ Setpoint Temperature object.
o If set to no” the setpoint temperature limits for the Control_ Setpoint Temperature object will be the
default: 16ºC for the lower limit and 32ºC for the upper limit.
o If set to “yes” it is possible to define temperature limits for the Control_ Setpoint Temperature object.
Control_ Set Temp Lower limit (ºC)
This parameter lets to define the lower limit for the setpoint temperature.
Control_ Set Temp Upper limit (ºC)
This parameter lets to define the upper limit for the setpoint temperature.
Important: If a setpoint temperature above the upper defined limit (or below the lower defined limit) is sent
through the Control_ Setpoint Temperature object, it will be ALWAYS applied the limit defined.
Important: When limits are enabled, any setpoint temperature sent to the AC (even through scenes, special
modes, etc.) will be limited.
5.7.3 Set Point - Periodic sending time
This parameter lets you change the interval of time (in seconds, from 0 to 255) at the end of which the AC
setpoint temperature is sent to the KNX bus. For a “0” value, the AC setpoint temperature will ONLY be sent
on change. The AC setpoint temperature is sent through the communication object Status_ AC Setpoint Temp.
5.7.4 Ambient - Transmission of “Status_ Intesis Ref Temp”
This parameter lets to you choose if the Intesis reference temperature will be sent only cyclically”, only on
change” or “cyclically and on change”. The Intesis reference temperature is sent through the communication
object Status_ Intesis Reference Temperature.
5.7.5 Ambient - Periodic sending time
This parameter will only be available for the “only cylically” and “cyclically and on change” options, and lets
you change the interval of time (in seconds, from 1 to 255) at the end of which the Intesis reference temperature
is sent to the KNX bus.
Up / Increase
Down / Decrease
16ºC
17ºC
32ºC
31ºC
(Upper limit)