o If set to “no” the communication objects will not be shown.
o If set to yes” the communication objects and a new parameter will appear. To store a scene through
the byte-type object, a value from “128” to “132” has to be sent to the object, correponding each one
to a different scene (i.e. 128 = Scene 1; 132 = Scene 5).
Enable use of bit objects for storing scenes (from bus)
If set to “no” the objects will not be shown.
If set to “yes” the Control_ Store Scene objects for storing scenes will appear. To store a scene by
using these objects, a “1” value has to be sent to the scene’s object we want to store (i.e. to store scene
4, a “1” has to be sent to the Control_ Store Scene 4 object).
5.8.3 Enable use of bit-field objects for save
This parameter shows/hides the Control_ Execute Scene bit-type communication objects.
o If set to “no” the communication objects will not be shown.
o If set to “yes” the communication objects will appear. To execute a scene by using these objects, a
“1” value has to be sent to the scene’s object we want to execute (i.e. to execute scene 4, a “1” has to
be sent to the Control_ Execute Scene 4 object).
5.8.4 Enable use of bit-field objects for execute
This parameter shows/hides the Control_ Execute Scene bit-type communication objects.
o If set to “no” the communication objects will not be shown.
o If set to “yes” the communication objects will appear. To execute a scene by using these objects, a
“1” value has to be sent to the scene’s object we want to execute (i.e. to execute scene 4, a “1” has to
be sent to the Control_ Execute Scene 4 object).
5.8.5 Scene “x” preset
This parameter lets you define a preset for a scene (the following description is valid for all the scenes).
o If set to “no” the preset for the scene “x” will be disabled.