Instructions
Intesis
TM
KNX – IR Universal AC
User's manual r1.3 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
33 / 46
o If set to “yes” the preset will be enabled. When a scene is executed the values configured in the preset
will be aplied.
Important: If a scene’s preset is enabled, will not be possible to modify (store) the scene from the KNX
bus.
➢ Scene “x” / Value for On-Off
This parameter lets you choose the power of the indoor unit when the scene is executed. The following
options are available: “ON”, “OFF” or “(unchanged)”.
➢ Scene “x” / Value for Mode
This parameter lets you choose the mode of the indoor unit when the scene is executed. The following
options are available: “AUTO”, “HEAT”, “COOL”, “FAN”, “DRY”, or “(unchanged)”.
➢ Scene “x” / Value for Fan Speed
This parameter lets you choose the fan speed of the indoor unit when the scene is executed. The
following options are available: “SPEED 1”, “SPEED 2”… “SPEED N”, or “(unchanged)”.
➢ Scene “x” / Value for Vane Up-Down
This parameter lets you choose the vane position of the indoor unit when the scene is executed. The
following options are available: “POSITION 1”, “POSITION 2”… “POSITION N”, “SWIRL”, “SWING”
or “(unchanged)”.
➢ Scene “x” / Value for Vane Left-Right
This parameter lets you choose the vane position of the indoor unit when the scene is executed. The
following options are available: “POSITION 1”, “POSITION 2”… “POSITION N”, “SWIRL”, “SWING”
or “(unchanged)”.
➢ Scene “x” / Value for Setp Temp (ºC)
This parameter lets you choose the setpoint temperature of the indoor unit when the scene is executed.
The following options are available: from “16ºC” to “32ºC” (both included), or “(unchanged)”.
Important: If any preset value is configured as “(unchanged)”, the execution of this scene will not
change current status of this feature in the AC unit.
Important: When a scene is executed, Status_ Current Scene object shows the number of this scene.
Any change in previous items does Status_ Current Scene show “No Scene”. Only changes on items
marked as “(unchanged)” will not disable current scene.
Enable use of Open Window
This parameter shows/hides the Control_ Window Contact Input communication object which lets you Start/Stop
a timeout to switch off the indoor unit.