o If set to “no” the object will not be shown.
o If set to “yes” the Control_ Window Contact Input object will appear. If a “1” value is sent to this object,
and the indoor unit is already turned on, the switch-off timeout will begin. If a “0” value is sent to this
object, the switch-off timeout will stop.
➢ Input Object
This parameter lets you choose between the datapoints 0-Open / 1-Closed Window [DPT_1.009] and
0-Stop / 1-Start Timeout [DPT_1.010] for the Control_ Switch Off Timeout.
➢ Timeout (min)
This parameter lets you select how much time (in minutes) to wait before switching off the indoor unit.
➢ Reload last Value
If set to “no”, once the switch-off timeout is stopped, any value will be reloaded.
If set to “yes”, once the switch-off timeout is stopped, the last On/Off value sent will be reloaded.
• If a “1” value is sent to the Control_ Window Contact Input object after the timeout period, the
indoor unit will turn on.
• If a “0” value is sent to the Control_ Switch Off Timeout after the timeout period, no action will
be performed.
➢ Lock ON when Open
If set to “no”, On/Off commands while the window is open will be accepted.
• If a “1” value is sent to the Control_ Switch Off Timeout object the switch-off timeout period will
begin again.
• If a “0” value is sent to the Control_ Switch Off Timeout object, no action will be performed.
If set to “yes”, On/Off commands, while the window is open, will be saved (but not applied). These
commands will be used in the next parameter if set to “yes”.