Enable use of Occupancy function
This parameter shows/hides the Control_ Occupancy Input communication object which lets you apply different
parameters to the indoor unit depending on the presence/no presence in the room.
o If set to “no” the object will not be shown.
o If set to “yes” the Control_ Occupancy object and new parameters will appear. If a “1” value is sent to
this object (no room occupancy), the timeout will begin. If a “0” value is sent to this object, the timeout
will stop.
➢ Timeout to apply action (minutes)
This parameter lets you choose how much time to wait (in minutes) before executing the action specified
in the next parameter (“Action after timeout elapsed”).
➢ Action
When Switch Off AC is selected, once the timeout has elapsed, the indoor unit will be turned off.
When Apply Preset Delta is selected, once the timeout has elapsed, a delta temperature will be applied
to save energy (decreasing the setpoint when in Heat mode or increasing the setpoint when in Cool
mode). Also new parameters will appear.
➢ Temp delta decreases (HEAT) or increase (COOL) (ºC)
This parameter lets configure the delta temperature (increase or decrease) that will be applied
when the timeout has elapsed.
Important: When there is occupancy again after the application of a delta, the same delta will be applied
inversely. (i.e. In a room with AC in cool mode and 25ºC setpoint temperature, a +2ºC delta is applied
after the occupancy timeout, setting the setpoint at 27ºC because there is no occupancy in the room. If