Instructions

Intesis
TM
KNX IR Universal AC
User's manual r1.2 eng
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
44 / 46
65
Control_ Store Scene3
1 bit
DPT_Bool
1.002
W
1 - Store Scene
66
Control_ Store Scene4
1 bit
DPT_Bool
1.002
W
1 - Store Scene
67
Control_ Store Scene5
1 bit
DPT_Bool
1.002
W
1 - Store Scene
68
Control_ Execute Scene1
1 bit
DPT_Bool
1.002
W
1 - Execute Scene
69
Control_ Execute Scene2
1 bit
DPT_Bool
1.002
W
1 - Execute Scene
70
Control_ Execute Scene3
1 bit
DPT_Bool
1.002
W
1 - Execute Scene
71
Control_ Execute Scene4
1 bit
DPT_Bool
1.002
W
1 - Execute Scene
72
Control_ Execute Scene5
1 bit
DPT_Bool
1.002
W
1 - Execute Scene
Disabling
73
Control_ Disable Input 1
1 bit
DPT_Bool
1.002
W
T
0 - Enable; 1 - Disable
Control_ Disable Input 1
1 bit
DPT_Enable
1.003
W
T
0 - Disable; 1 - Enable
74
Control_ Disable Input 2
1 bit
DPT_Bool
1.002
W
T
0 - Enable; 1 - Disable
Control_ Disable Input 2
1 bit
DPT_Enable
1.003
W
T
0 - Disable; 1 - Enable
STATUS OBJECTS
On/Off
75
Status_ On/Off
1 bit
DPT_Switch
1.001
R
T
0 - Off; 1-On
Mode
76
Status_ Mode
1 byte
DPT_HVACContrMode
20.105
R
T
0 - Auto; 1 - Heat; 3 - Cool; 9 - Fan; 14 - Dry
77
Status_ Mode Cool/Heat
1 bit
DPT_Heat/Cool
1.100
R
T
0 - Cool; 1 - Heat
78
Status_ Mode Auto
1 bit
DPT_Bool
1.002
R
T
1 - Auto
79
Status_ Mode Heat
1 bit
DPT_Bool
1.002
R
T
1 - Heat
80
Status_ Mode Cool
1 bit
DPT_Bool
1.002
R
T
1 - Cool
81
Status_ Mode Fan
1 bit
DPT_Bool
1.002
R
T
1 - Fan
82
Status_ Mode Dry
1 bit
DPT_Bool
1.002
R
T
1 - Dry
83
Status_ Mode Text
14 byte
DPT_String_8859_1
16.001
R
T
ASCII String
Fan Speed
84
Status_ Fan Speed / N Speeds
1 byte
DPT_Scaling
5.001
R
T
100*(n+0,5)/N %
Status_ Fan Speed / N Speeds
1 byte
DPT_Enumerated
5.010
R
T
1 - Speed1; 2 - Speed2; 3 - Speed3; 4 - Speed4;
5 - Speed5; 6 - Speed6; 7 - Speed7
85
Status_ Fan Speed Man/Auto
1 bit
DPT_Bool
1.002
R
T
0 - Manual; 1 - Auto
86
Status_ Fan Speed 1
1 bit
DPT_Bool
1.002
R
T
1 - Speed 1