Instructions

Intesis
TM
KNX IR Universal AC
User's manual r1.2 eng
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
45 / 46
87
Status_ Fan Speed 2
1 bit
DPT_Bool
1.002
R
T
1 - Speed 2
88
Status_ Fan Speed 3
1 bit
DPT_Bool
1.002
R
T
1 - Speed 3
89
Status_ Fan Speed 4
1 bit
DPT_Bool
1.002
R
T
1 - Speed 4
90
Status_ Fan Speed 5
1 bit
DPT_Bool
1.002
R
T
1 - Speed 5
91
Status_ Fan Speed 6
1 bit
DPT_Bool
1.002
R
T
1 - Speed 6
92
Status_ Fan Speed 7
1 bit
DPT_Bool
1.002
R
T
1 - Speed 7
93
Status_ Fan Speed Text
14 byte
DPT_String_8859_1
16.001
R
T
ASCII String
Vanes
94
Status_ Vane Up-Down / 8 pos
1 byte
DPT_Scaling
5.001
R
T
100*(n+0,5)/N %
Status_ Vane Up-Down / 8 pos
1 byte
DPT_Enumerated
5.010
R
T
1 - Pos1; 2 - Pos2; 3 - Pos3; 4 - Pos4; 5 - Pos5;
6 - Pos6; 7 - Pos7; 8 - Pos8
95
Status_ Vane Man/Auto
1 bit
DPT_Bool
1.002
R
T
0 - Manual; 1 - Auto
96
Status_ Vane Up-Down Pos1
1 bit
DPT_Bool
1.002
R
T
1 - Position 1
97
Status_ Vane Up-Down Pos2
1 bit
DPT_Bool
1.002
R
T
1 - Position 2
98
Status_ Vane Up-Down Pos3
1 bit
DPT_Bool
1.002
R
T
1 - Position 3
99
Status_ Vane Up-Down Pos4
1 bit
DPT_Bool
1.002
R
T
1 - Position 4
100
Status_ Vane Up-Down Pos5
1 bit
DPT_Bool
1.002
R
T
1 - Position 5
101
Status_ Vane Up-Down Pos6
1 bit
DPT_Bool
1.002
R
T
1 - Position 6
102
Status_ Vane Up-Down Pos7
1 bit
DPT_Bool
1.002
R
T
1 - Position 7
103
Status_ Vane Up-Down Pos8
1 bit
DPT_Bool
1.002
R
T
1 - Position 8
104
Status_ Vane Up-Down Swing
1 bit
DPT_Bool
1.002
R
T
0 - Stop; 1 - Swing
105
Status_ Vane Up-Down Swirl
1 bit
DPT_Bool
1.002
R
T
0 - Stop; 1 - Swirl
106
Status_ Vane Up-Down Wide
1 bit
DPT_Bool
1.002
R
T
0 - Stop; 1 - Wide
107
Status_ Vane Up-Down Text
14 byte
DPT_String_8859_1
16.001
R
T
ASCII String
108
Status_ Vane Left-Right / 8 pos
1 byte
DPT_Scaling
5.001
R
T
100*(n+0,5)/N %
Status_ Vane Left-Right / 8 pos
1 byte
DPT_Enumerated
5.010
R
T
1 - Pos1; 2 - Pos2; 3 - Pos3; 4 - Pos4; 5 - Pos5;
6 - Pos6; 7 - Pos7; 8 - Pos8
109
Status_ Vane Left-Right Man/Auto
1 bit
DPT_Bool
1.002
R
T
0 - Manual; 1 - Auto
110
Status_ Vane Left-Right Pos1
1 bit
DPT_Bool
1.002
R
T
1 - Position 1