Compatible with Domestic line models USER MANUAL Issue date: 12/2017 r2.
IntesisTM INMBSDAI001I000 User’s Manual r2.3 EN Important User Information Disclaimer The information in this document is for informational purposes only. Please inform HMS Industrial Networks of any inaccuracies or omissions found in this document. HMS Industrial Networks disclaims any responsibility or liability for any errors that may appear in this document. HMS Industrial Networks reserves the right to modify its products in line with its policy of continuous product development.
IntesisTM INMBSDAI001I000 User’s Manual r2.3 EN Modbus RTU (EIA-485) Interface for Daikin air conditioners. Compatible with Domestic line models. ORDER CODE INMBSDAI001I000 LEGACY ORDER CODE DK-AC-MBS-1 © HMS Industrial Networks S.L.U - All rights reserved This information is subject to change without notice URL https://www.intesis.
IntesisTM INMBSDAI001I000 User’s Manual r2.3 EN INDEX 1. Presentation ........................................................................................................ 5 2. Connection .......................................................................................................... 6 2.1 Connect to the AC indoor unit ........................................................................... 6 2.2 Connection to the EIA-485 bus ...............................................................
IntesisTM INMBSDAI001I000 User’s Manual r2.3 EN 1. Presentation The INMBSDAI001I000 interface allows a complete and natural integration of Daikin air conditioners into Modbus RTU (EIA-485) networks. Compatible with Domestic line models. Reduced dimensions. 93 x 53 x 58 mm 3.7” x 2.1” x 2.3” • Quick and easy installation. Mountable on DIN rail, wall, or even inside the indoor unit on some models of AC. • External power not required. • Direct connection to Modbus RTU (EIA-485) networks.
IntesisTM INMBSDAI001I000 User’s Manual r2.3 EN 2. Connection The interface comes with a specific cable and connectors to establish direct connection to the AC indoor unit. It comes as well with a plug-in terminal block of 2 poles to establish direct connection with the Modbus RTU EIA-485 network. 2.1 Connect to the AC indoor unit To connect the INMBSDAI001I000 interface with the AC indoor unit you must follow these steps: Disconnect Mains Power from the AC unit.
IntesisTM INMBSDAI001I000 User’s Manual r2.3 EN 3. Quick Start Guide 1. Disconnect the air conditioning from the Mains Power. 2. Attach the interface next to the AC indoor unit (wall mounting) following the instructions of the diagram below or install it inside the AC indoor unit (respect the safety instructions given above). 3. Connect the connection cable included with the interface between the interface and the AC indoor unit following the instructions of the diagram. 4.
IntesisTM INMBSDAI001I000 User’s Manual r2.3 EN 4. Modbus Interface Specification 4.1 Modbus physical layer INMBSDAI001I000 implements a Modbus RTU (Slave) interface, to be connected to an EIA485 line. It performs an 8N2 communication (8 data bits, no parity and 2 stop bit) with several available baud rates (2400 bps, 4800 bps, 9600 bps -default-, 19200 bps, 38400 bps, 57600 bps, 76800 bps and 115200 bps). It also supports 8N1 communication (8 data bits, no parity and 1 stop bit). 4.
IntesisTM INMBSDAI001I000 Register Address Register Address (protocol address) (PLC address) User’s Manual r2.3 EN R/W Description AC unit Temperature reference 5 6 R 6 7 R/W ▪ ▪ ▪ 1,2,3 -32678 (Initialization value) 10..38 ºC (ºC/x10ºC) 50..
IntesisTM INMBSDAI001I000 User’s Manual r2.3 EN ▪ 97 98 R/W 4: Continuous Block Periodic Sendings ▪ ▪ 4,7,8 0: Non-blocked (Default value) 1: Blocked 4.2.2 Configuration Registers Register Address (protocol address) Register Address (PLC address) R/W 13 14 R/W Description “Open Window” switch-off timeout ▪ ▪ 9 0..
IntesisTM INMBSDAI001I000 User’s Manual r2.3 EN This register reports the temperature that is currently used by the Daikin indoor unit as the reference of its own control loop. Depending on the configuration of the indoor unit, this value can be the temperature reported by the sensor on the return path of the Daikin indoor unit or the sensor of its Remote Controller. It is a read-only register (Modbus functions 3 or 4).
IntesisTM INMBSDAI001I000 User’s Manual r2.3 EN scenario, the setpoint value shown or written in register 4/5 will always be the same as the current setpoint value of the indoor unit. o • Notice that, the use of the “external temperature reference” (register 22/23) (e.g., writing a value different from -32768 / 0x8000 in it) has the following relevant consequences: ▪ The mechanism of “Virtual Temperature” is applied.
IntesisTM INMBSDAI001I000 User’s Manual r2.3 EN 4.3 DIP-switch Configuration Interface All the configuration values on INMBSDAI001I000 can be written and read from Modbus interface. Otherwise, some of them can also be setup from its on-board DIP-switch interface.
IntesisTM INMBSDAI001I000 User’s Manual r2.3 EN SW3/SW4 – Baud rate configuration SW3-P7..8 ON SW4-P3 Description ON 2400bps ON ON ON ON ON ON 4800bps 9600bps (Default value) 19200bps ON ON ON ON ON ON ON 38400bps 57600bps 76800bps ON 115200bps Table 4.2 SW3-SW4: Modbus baud rate © HMS Industrial Networks S.L.U - All rights reserved This information is subject to change without notice URL https://www.intesis.
IntesisTM INMBSDAI001I000 User’s Manual r2.3 EN SW3 – Modbus Slave address Add SW3-P1..
IntesisTM INMBSDAI001I000 User’s Manual r2.3 EN 4.4 Implemented Functions INMBSDAI001I000 implements the following standard Modbus functions: ▪ 3: Read Holding Registers ▪ 4: Read Input Registers ▪ 6: Write Single Register ▪ 16: Write Multiple Registers (Despite this function is allowed, the interface does not allow to write operations on more than 1 register with the same request, this means that length field should always be 1 when this function is being used in case of writing) 4.
IntesisTM INMBSDAI001I000 User’s Manual r2.3 EN 5. Mechanical and electrical features Enclosure Plastic, type PC (UL 94 V-0) Net dimensions (dxwxh): 93 x 53 x 58 mm / 3.7” x 2.1” x 2.3” Color: Light Grey. RAL 7035 Operation Temperature 0ºC to +60ºC Weight 85 g. Stock Temperature -20ºC to +85ºC Mounting Wall DIN rail EN60715 TH35.
IntesisTM INMBSDAI001I000 User’s Manual r2.3 EN 6. List of supported AC Unit Types A list of Daikin indoor unit model´s references compatible with INMBSDAI001I000 and its available features can be found in: https://www.intesis.com/docs/compatibilities/inxxxdai001xx00_compatibility © HMS Industrial Networks S.L.U - All rights reserved This information is subject to change without notice URL https://www.intesis.
IntesisTM INMBSDAI001I000 User’s Manual r2.3 EN 7.
IntesisTM INMBSDAI001I000 73 74 75 76 77 79 80 81 82 83 84 87 91 92 93 95 96 97 98 99 100 H8 H9 HA HH HC HE HF F0 F1 F2 F3 F6 FA FH FC FE FF J0 J1 J2 J3 101 J4 102 103 104 105 J5 J6 J7 J8 106 J9 107 108 109 111 112 113 116 117 JA JH JC JE JF L0 L3 L4 118 L5 119 L6 120 121 L7 L8 122 L9 123 LA 125 LC 129 130 132 133 134 135 136 142 145 P0 P1 P3 P4 SW4 SW1 SW3 PJ U0 System © HMS Industrial Networks S.L.
IntesisTM INMBSDAI001I000 146 147 148 U1 U2 U3 149 U4 150 U5 151 U6 152 U7 153 U8 154 U9 155 UA 156 UH 157 158 UC UJ 159 UE 160 UF 209 210 211 212 213 214 217 219 220 221 222 223 224 226 60 61 62 63 64 65 68 6A 6H 6C 6J 6E 6F 51 227 52 228 229 241 242 243 244 245 258 259 260 261 262 53 54 40 41 42 43 44 31 32 33 34 35 Others © HMS Industrial Networks S.L.U - All rights reserved This information is subject to change without notice User’s Manual r2.
IntesisTM INMBSDAI001I000 263 267 268 269 339 36 3A 3H 3C M2 345 M8 347 349 65535 (-1) MA MC N/A User’s Manual r2.