4: Continuous
97
98
R/W
Block Periodic Sendings
4,7,8
0: Non-blocked (Default value)
1: Blocked
4.2.2 Configuration Registers
Register Address
(protocol address)
Register Address
(PLC address)
R/W
Description
13
14
R/W
“Open Window” switch-off timeout
9
0..30 (minutes)
Factory setting: 30 (minutes)
14
15
R
Modbus RTU Baud rate
2400bps
4800bps
9600bps (Default)
19200bps
38400bps
57600bps
76800bps
115200bps
15
16
R
Device's Modbus Slave address
1..63
21
22
R
Max number of fan speeds
Value is always 5
49
50
R
Device ID: 0x0701
50
51
R
Software version
4.2.3 Considerations on Temperature Registers
AC unit temperature setpoint (R/W)
(register 4 in Protocol address / register 5 in PLC address):
This is the adjustable temperature setpoint value that must be required by the User.
This register can be read (Modbus function 3 or 4) or written (Modbus functions 6 or
16). A Remote Controller connected to the Daikin indoor unit will report the same
temperature setpoint value as this register. This will apply when no AC unit’s
external reference temperature is provided from INMBSDAI001I000 (see details for
register 22/23 below).
AC unit temperature reference (R)
(register 5 in Protocol address / register 6 in PLC address):
7
If the register is configured as “0:Non-blocked”, all commands received from Modbus will be sent to the AC system. If “1:
Blocked”, commands from Modbus will only be sent to the AC system if they differ from the previous value (values sent on change).
8
The register applies to firmware version 1.5 onwards
9
Once window contact is open, a count-down to switch off the AC Unit will start from this configured value.