▪  4: Continuous 
97 
98 
R/W 
Block Periodic Sendings 
4,7,8
▪  0: Non-blocked (Default value) 
▪  1: Blocked 
4.2.2 Configuration Registers 
Register Address 
(protocol address) 
Register Address 
(PLC address) 
R/W 
Description 
13 
14 
R/W 
“Open Window” switch-off timeout 
9
▪  0..30 (minutes) 
▪  Factory setting: 30 (minutes) 
14 
15 
R 
Modbus RTU Baud rate 
▪  2400bps 
▪  4800bps 
▪  9600bps (Default) 
▪  19200bps 
▪  38400bps 
▪  57600bps 
▪  76800bps 
▪  115200bps 
15 
16 
R 
Device's Modbus Slave address 
▪  1..63 
21 
22 
R 
Max number of fan speeds 
▪  Value is always 5 
49 
50 
R 
Device ID: 0x0701 
50 
51 
R 
Software version 
4.2.3 Considerations on Temperature Registers 
•  AC unit temperature setpoint (R/W)  
(register 4 – in Protocol address / register 5 – in PLC address): 
This is the adjustable temperature setpoint value that must be required by the User. 
This register can be read (Modbus function 3 or 4) or written (Modbus functions 6 or 
16).  A  Remote  Controller  connected  to  the  Daikin  indoor  unit  will  report  the  same 
temperature  setpoint  value  as  this  register.  This  will  apply  when  no  AC  unit’s 
external  reference temperature is provided from  INMBSDAI001I000 (see details for 
register 22/23 below). 
•  AC unit temperature reference (R) 
(register 5 – in Protocol address / register 6 – in PLC address): 
7
  If  the  register  is  configured  as  “0:Non-blocked”,  all  commands  received  from  Modbus  will  be  sent  to  the  AC  system.  If  “1: 
Blocked”, commands from Modbus will only be sent to the AC system if they differ from the previous value (values sent on change). 
8
 The register applies to firmware version 1.5 onwards 
9
 Once window contact is open, a count-down to switch off the AC Unit will start from this configured value. 