Register Address
(protocol address)
Register Address
(PLC address)
R/W
Description
5
6
R
AC unit Temperature reference
1,2,3
-32678 (Initialization value)
10..38 ºC (ºC/x10ºC)
50..100 ºF
6
7
R/W
Window Contact
0: Closed (Default Value)
1: Open
7
8
R/W
INMBSDAI001I000 Disablement
4
0: INMBSDAI001I000 enabled (Default
Value)
1: INMBSDAI001I000 disabled
8
9
R/W
AC Remote Control Disablement
4
0: Remote Control enabled (Default)
1: Remote Control disabled
9
10
R/W
AC unit Operation Time
4
0..65535 (hours). Counts the time the
AC unit is in “On” state.
10
11
R
AC unit Alarm Status
0: No alarm condition
1: Alarm condition
11
12
R
Error Code
5
0: No error present
65535 (-1 if it is read as signed value):
Error in the communication of
INMBSDAI001I000 with the AC unit
Any other error present, see the table at
the end of this document.
22
23
R/W
Indoor unit ambient temperature from
external sensor (at Modbus side)
1,2,3,6
-32768: (Initialization value). No
temperature is being provided from an
external sensor.
Any other: (ºC/x10ºC/ºF)
23
24
R
AC Real temperature setpoint
1,2,3,6
-32678 (Initialization value)
COOL
18..32 ºC (ºC/x10ºC)
64..92 ºF
HEAT
16..30 ºC (ºC/x10ºC)
61..88 ºF
AUTO
18..30 ºC (ºC/x10ºC)
64..88 ºF
26
27
R/W
AC unit Left/Right Vane Position
1
0: Auto (Default Value)
10: Swing
28
29
R/W
AC Humidification Value
1
0: Off
1: Low Humidification
2: Medium Humidification
3: High Humidification
4
This value is stored in non-volatile memory
5
See section 7 for possible error codes and their explanation
6
See section 4.2.3 for more information