Instructions
Intesis
TM
INMBSDAI001I000
User’s Manual r2.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
9 / 22
Register Address
(protocol address)
Register Address
(PLC address)
R/W
Description
5
6
R
AC unit Temperature reference
1,2,3
▪ -32678 (Initialization value)
▪ 10..38 ºC (ºC/x10ºC)
▪ 50..100 ºF
6
7
R/W
Window Contact
▪ 0: Closed (Default Value)
▪ 1: Open
7
8
R/W
INMBSDAI001I000 Disablement
4
▪ 0: INMBSDAI001I000 enabled (Default
Value)
▪ 1: INMBSDAI001I000 disabled
8
9
R/W
AC Remote Control Disablement
4
▪ 0: Remote Control enabled (Default)
▪ 1: Remote Control disabled
9
10
R/W
AC unit Operation Time
4
▪ 0..65535 (hours). Counts the time the
AC unit is in “On” state.
10
11
R
AC unit Alarm Status
▪ 0: No alarm condition
▪ 1: Alarm condition
11
12
R
Error Code
5
▪ 0: No error present
▪ 65535 (-1 if it is read as signed value):
Error in the communication of
INMBSDAI001I000 with the AC unit
▪ Any other error present, see the table at
the end of this document.
22
23
R/W
Indoor unit ambient temperature from
external sensor (at Modbus side)
1,2,3,6
▪ -32768: (Initialization value). No
temperature is being provided from an
external sensor.
▪ Any other: (ºC/x10ºC/ºF)
23
24
R
AC Real temperature setpoint
1,2,3,6
▪ -32678 (Initialization value)
COOL
▪ 18..32 ºC (ºC/x10ºC)
▪ 64..92 ºF
HEAT
▪ 16..30 ºC (ºC/x10ºC)
▪ 61..88 ºF
AUTO
▪ 18..30 ºC (ºC/x10ºC)
▪ 64..88 ºF
26
27
R/W
AC unit Left/Right Vane Position
1
▪ 0: Auto (Default Value)
▪ 10: Swing
28
29
R/W
AC Humidification Value
1
▪ 0: Off
▪ 1: Low Humidification
▪ 2: Medium Humidification
▪ 3: High Humidification
4
This value is stored in non-volatile memory
5
See section 7 for possible error codes and their explanation
6
See section 4.2.3 for more information