Compatible with VRV and SKY line air conditioners commercialized by Daikin USER MANUAL Issue date: 10/2020 r3.
IntesisTM INMBSDAI001R000 User’s Manual r3.8 EN Important User Information Disclaimer The information in this document is for informational purposes only. Please inform HMS Industrial Networks of any inaccuracies or omissions found in this document. HMS Industrial Networks disclaims any responsibility or liability for any errors that may appear in this document. HMS Industrial Networks reserves the right to modify its products in line with its policy of continuous product development.
IntesisTM INMBSDAI001R000 User’s Manual r3.8 EN Modbus RTU (EIA-485) Interface for Daikin air conditioners Compatible with VRV commercialized by Daikin ORDER CODE INMBSDAI001R000 and SKY line air conditioners LEGACY ORDER CODE DK-RC-MBS-1 © HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice URL https://www.intesis.
IntesisTM INMBSDAI001R000 User’s Manual r3.8 EN INDEX 1. Presentation .......................................................................................................... 5 2. Connection ............................................................................................................ 6 2.1 Connect to the AC indoor unit ............................................................................... 6 2.2 Connection to the EIA-485 bus ................................................
IntesisTM INMBSDAI001R000 User’s Manual r3.8 EN 1. Presentation The INMBSDAI001R000 interfaces allow a complete and natural integration of Daikin air conditioners into Modbus RTU (EIA-485) networks. Compatible with all SKY Air and VRV models commercialized by Daikin. Check the Section 6 to obtain more information. Reduced dimensions. 93 x 53 x 58 mm 3.7” x 2.1” x 2.3” • Quick and easy installation. • External power not required. • Direct connection to Modbus RTU (EIA-485) networks.
IntesisTM INMBSDAI001R000 User’s Manual r3.8 EN 2. Connection The interface comes with a plug-in terminal block of 2 poles to establish direct connection with the AC indoor unit. It comes as well with a plug-in terminal block of 2 poles to establish direct connection with the Modbus RTU EIA-485 network. 2.1 Connect to the AC indoor unit The INMBSDAI001R000 connects directly to the Daikin P1P2 Bus, which is not provided within the interface.
IntesisTM INMBSDAI001R000 User’s Manual r3.8 EN 2.2 Connection to the EIA-485 bus Connect the EIA-485 bus wires to the plug-in terminal block (the one of two poles) of INMBSDAI001R000 and keep the polarity on this connection (A+ and B-). Make sure that the maximum distance to the bus is 1,200 meters (3,937 ft). Loop or star typologies are not allowed in the case of the EIA-485 bus. A terminator resistor of 120Ω must be present at each end of the bus to avoid signal reflections.
IntesisTM INMBSDAI001R000 User’s Manual r3.8 EN 4. Modbus Interface Specification 4.1 Modbus physical layer INMBSDAI001R000 implements a Modbus RTU (Slave) interface, to be connected to an EIA-485 line. It performs 8N2 communication (8 data bits, no parity and 2 stop bit) with several available baud rates (2400 bps, 4800 bps, 9600 bps -default-, 19200 bps, 38400 bps, 57600 bps, 76800 bps and 115200 bps). It also supports 8N1 communication (8 data bits, no parity and 1 stop bit). 4.
IntesisTM INMBSDAI001R000 User’s Manual r3.8 EN Register Address (protocol address) Register Address (PLC address) R/W 6 7 R/W Description Window Contact ▪ ▪ 0: Closed (Default) 1: Open INMBSDAI001R000 Disablement 7 8 R/W ▪ ▪ 8 9 R/W 9 10 R/W 10 11 R 0: INMBSDAI001R000 enabled (Default value) 1: INMBSDAI001R000 disabled AC Remote Control Disablement ▪ ▪ 12 R 4 0..65535 (hours). Counts the time the AC unit is in “On” state.
IntesisTM INMBSDAI001R000 User’s Manual r3.8 EN 4.2.2 Configuration Registers Register Address (protocol address) Register Address (PLC address) 13 14 R/W R/W Description “Open Window” switch-off timeout ▪ ▪ 10 0..30 (minutes) Factory setting: 30 (minutes) Modbus RTU baud-rate 14 15 R 15 16 R 21 48 49 50 22 49 50 51 R R R R 81 82 R ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ 2400bps 4800bps 9600bps (Default) 19200bps 38400bps 57600bps 76800bps 115200bps Modbus Slave Address ▪ 1..
IntesisTM INMBSDAI001R000 User’s Manual r3.8 EN 4.2.3 Considerations on Temperature Registers • AC unit temperature setpoint (R/W) (register 4 – in Protocol address / register 5 – in PLC address): This is the adjustable temperature setpoint value that must be required by the user. This register can be read (Modbus function 3 or 4) or written (Modbus functions 6 or 16).
IntesisTM INMBSDAI001R000 User’s Manual r3.
IntesisTM INMBSDAI001R000 User’s Manual r3.8 EN This register always informs about the current temperature setpoint which is being used by the indoor unit and it is also includes the temperature setpoint that will be shown by an additional remote controller from Daikin connected to the indoor unit, if it is present on the system.
IntesisTM INMBSDAI001R000 User’s Manual r3.8 EN 4.3 DIP-switch Configuration Interface All the configuration values on INMBSDAI001R000 can be written and read from Modbus interface. Otherwise, some of them can also be setup from its on-board DIP-switch interface.
IntesisTM INMBSDAI001R000 User’s Manual r3.8 EN SW3/SW4 – Baud rate configuration SW3-P7..8 ON SW4-P3 Description ON 2400bps ON ON ON ON ON ON 4800bps 9600bps (Default value) 19200bps ON ON ON ON ON ON ON 38400bps 57600bps 76800bps ON 115200bps Table 4.2 SW3-SW4: Modbus baud rate SW4 – Degrees/Decidegrees (x10), temperature magnitude (ºC/ºF) and EIA-485 termination resistor. SW4-P1..
IntesisTM INMBSDAI001R000 User’s Manual r3.8 EN SW3 – Modbus Slave address Add SW3-P1..6 Add SW3-P1..6 Add SW3-P1..6 Add SW3-P1..6 Add SW3-P1..
IntesisTM INMBSDAI001R000 User’s Manual r3.8 EN 4.4 Implemented Functions INMBSDAI001R000 implements the following standard Modbus functions: ▪ 3: Read Holding Registers ▪ 4: Read Input Registers ▪ 6: Write Single Register ▪ 16: Write Multiple Registers (Despite this function is allowed, the interface does not allow to write operations on more than 1 register with the same request, this means that length field should be always be 1 when this function is being used in case of writing) 4.
IntesisTM INMBSDAI001R000 User’s Manual r3.8 EN 4.6 EIA-485 bus. Termination resistors and Fail-Safe Biasing mechanism EIA-485 bus requires a 120Ω terminator resistor at each end of the bus to avoid signal reflections. In order to prevent fail status detected by the receivers, which are “listening” the bus, when all the transmitters’ outputs are in three-state (high impedance), it is also required a fail-safe biasing mechanism.
IntesisTM INMBSDAI001R000 User’s Manual r3.8 EN 5. Electrical and Mechanical features Enclosure Plastic, type PC (UL 94 V-0) Net dimensions (dxwxh): 93 x 53 x 58 mm / 3.7” x 2.1” x 2.3” Color: Light Grey. RAL 7035 Operation Temperature 0ºC to +60ºC Weight 85 g. Stock Temperature -20ºC to +85ºC Mounting Wall DIN rail EN60715 TH35.
IntesisTM INMBSDAI001R000 User’s Manual r3.8 EN 6. List of supported AC Unit Types. A list of Daikin indoor unit model’s references compatible with INMBSDAI001R000 and its available features can be found on this link: https://www.intesis.com/docs/compatibilities/inxxxdai001rx00_compatibility © HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice URL https://www.intesis.
IntesisTM INMBSDAI001R000 User’s Manual r3.8 EN 7.
IntesisTM INMBSDAI001R000 69 70 71 H4 H5 H6 72 H7 73 74 75 H8 H9 HA 76 HH 77 79 80 HC HE HF 81 F0 82 83 84 87 91 92 93 95 96 97 98 99 100 F1 F2 F3 F6 FA FH FC FE FF J0 J1 J2 J3 101 J4 102 103 104 J5 J6 J7 105 J8 106 J9 107 108 109 111 112 113 116 JA JH JC JE JF L0 L3 117 L4 118 L5 119 120 L6 L7 121 L8 122 L9 123 LA 125 LC Outdoor Unit © HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice User’s Manual r3.
IntesisTM INMBSDAI001R000 129 130 132 133 134 135 136 142 P0 P1 P3 P4 P5 P6 P7 PJ 145 U0 146 U1 147 U2 148 U3 149 U4 150 U5 151 U6 152 U7 153 U8 154 U9 155 UA 156 UH 157 158 UC UJ 159 UE 160 UF 209 210 211 212 213 214 217 219 220 221 222 60 61 62 63 64 65 68 6A 6H 6C 6J System System © HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice User’s Manual r3.
IntesisTM INMBSDAI001R000 223 224 226 6E 6F 51 227 52 228 229 241 242 243 244 245 258 259 260 261 262 263 267 268 269 339 53 54 40 41 42 43 44 31 32 33 34 35 36 3A 3H 3C M2 345 M8 347 MA 349 65535 (-1) MC N/A User’s Manual r3.
IntesisTM INMBSDAI001R000 User’s Manual r3.8 EN 8. Annex 1: Master/Slave of Operation Mode The Master/Slave of Operation mode only applies under the following conditions: 1. The AC system is VRV 2. The VRV system uses a Heat pump as outdoor unit 3. There more than one indoor unit in a unique system working at different modes (Table 8.1) If they are not matched the parameter is going to be ignored. The Heat pump outdoor unit of a VRV system can only work in one mode (either Heat, Cool or fan).